6-42 Mounting and Installation <strong>Rexroth</strong> <strong>Indra<strong>Drive</strong></strong><br />

Design<br />

Connection Cross Section<br />

X3, Mains Connection<br />

DANGER<br />

High electrical voltage! Danger to life, severe<br />

bodily harm by electric shock!<br />

Always operate the drive controller with plugged on<br />

⇒<br />

connector!<br />

<strong>HCS02.1</strong>E- Type Number of<br />

poles<br />

W0012 Screw terminal<br />

block<br />

W0028 Screw terminal<br />

block<br />

W0054 Screw terminal<br />

block<br />

W0070 Screw terminal<br />

block<br />

Fig. 6-43: Design<br />

Type of design<br />

4 Pins on device<br />

4 Pins on device<br />

4 Pins on device<br />

4 Pins on device<br />

HCS03.1E- Type No. of poles Type of design<br />

W0070 Connector 4 Screw connection<br />

W0100 Terminal block 3 Screw connection for<br />

M6 ring cable lugs<br />

W0150 Terminal block 3 Screw connection for<br />

M6 ring cable lugs<br />

W0210 Terminal block 3 Screw connection for<br />

M10 ring cable lug<br />

Fig. 6-44: Design<br />

Identification of the individual connections:<br />

Identification Significance<br />

L1 phase 1<br />

L2 phase 2<br />

L3 phase 3<br />

(PE) equipment grounding conductor<br />

Fig. 6-45: Identification of the individual connections mains connection<br />

Note: Only with single-phase operation: connect the connecting lines<br />

of the mains voltage supply L1 and N with the connections L1<br />

and L2.<br />

<strong>HCS02.1</strong>E- Cross section<br />

single-wire<br />

[mm²]<br />

Cross section<br />

multi-wire<br />

[mm²]<br />

Cross section<br />

in AWG<br />

W0012, W0028 0,2-4 0,2-4 24-10<br />

W0054, W0070 0,5-10 0,5-10 20-8<br />

Fig. 6-46: Connection cross section<br />