<strong>Rexroth</strong> <strong>Indra<strong>Drive</strong></strong> Commissioning and Parameterization 7-81<br />

Function<br />

Function<br />

Function<br />

Function<br />

DOK-INDRV*-FU*********-IB01-EN-P<br />

of holding system. When P-0-0547, Nominal load of holding system<br />

is exceeded, the error message F3116 Nominal load torque of holding<br />

system exceeded is output.<br />

P-0-0555, Status word of axis controller<br />

Input min/max: Default value: Unit:<br />

MPB: --- / --- --- --<br />

This parameter contains the following status information (messages)<br />

regarding axis control in the form of individual status bits:<br />

• velocity messages<br />

• limits that have been reached, i.e. information regarding an active<br />

limitation<br />

See also Functional Description "Limitations"<br />

See also Functional Description "Axis Control"<br />

P-0-0556, Config word of axis controller<br />

Input min/max: Default value: Unit:<br />

MPB: --- / --- 32769 --<br />

This parameter is used for configuring functions specific to axis control<br />

and setting the control performance.<br />

See also Functional Description "<strong>Drive</strong> Control - Axis Control (Closed-<br />

Loop Operation)"<br />

See also Functional Description "Performance Data"<br />

P-0-0568, Voltage boost<br />

Input min/max: Default value: Unit:<br />

MPB: 0,00 / 50,00 0,00 V eff<br />

By means of this parameter it is possible to increase the voltage at the<br />

base point of the U/f characteristic (in the case of standstill or very low<br />

speed of an asynchronous motor). The voltage required at the base point<br />

is determined on the basis of the motor data and provided by the<br />

controller.<br />

P-0-0569, Maximum stator frequency change<br />

Input min/max: Default value: Unit:<br />

MPB: 0,01 / 3000,00 200,00 Hz/s<br />

The maximum change of velocity with which the drive can follow the<br />

command values is determined by the motor and the sampling time of the<br />

stall protection loop. The limit value can be set with this parameter.<br />

P-0-0570, Stall protection loop proportional gain<br />

Input min/max: Default value: Unit:<br />

MPB: 0,00 / 500,00 100,00 %