5-4 Electrical Data <strong>Rexroth</strong> <strong>Indra<strong>Drive</strong></strong><br />

Limited Length of Motor Power Cables<br />

Limited Lengths of Motor Power<br />

Cables<br />

Documentation Motor Power<br />

Cables<br />

Keep in mind, that the allowed maximum motor cable length is depending<br />

on the switching frequency of the power output stage. On principle, the<br />

higher the switching frequency, the shorter the allowed cable length (in<br />

order to protect the drive controllers against overload).<br />

Note: Always use switching frequencies supported by the<br />

components of your drive system. Observe the technical data<br />

of the drive controllers and motors.<br />

See also Parameter Description "P-0-0001, Switching frequency of the<br />

power output stage".<br />

The lengths indicated in the table below are recommended as guide<br />

values (at an ambient temperature of ≤ 40 °C in accordance with<br />

EN 60 204).<br />

Allowed line lengths for motor connection without filter measures at<br />

motor output:<br />

PWM frequency [kHz]<br />

2 2)<br />

Max. allowed line length [m]<br />

Shielded line Unshielded line 1)<br />

100 175<br />

4 75 150<br />

8 38 150<br />

12 25 not allowed<br />

16 18 not allowed<br />

1) only allowed at HCS drive controllers<br />

2) depending on the drive controller<br />

Fig. 5-4: Line lengths<br />

Operation with unshielded motor cables of up to 150 m<br />

• aims at applications with "operation without encoder" (Open Loop)<br />

• does not include the control voltage lines to the motor<br />

• requires additional measures with regard to EMC on the part of the<br />

operating company<br />

Allowed line lengths for motor connection with additional components<br />

HMF or HML:<br />

PWM frequency [kHz]<br />

Max. allowed line length [m]<br />

Shielded line Unshielded line 1)<br />

4 2)<br />

75 200<br />

1) only allowed at HCS03 drive controllers<br />

2) higher PWM frequencies are not allowed<br />

Fig. 5-5: Line lengths<br />

The documentation "<strong>Rexroth</strong> Connection Cables; Selection Data" is<br />

available for selecting the motor power cables and other connections,<br />

such as encoder cables.<br />

<strong>Rexroth</strong> <strong>Indra<strong>Drive</strong></strong> drive systems have to be equipped with shielded<br />

motor power cables of the RKL line.<br />

DOK-INDRV*-FU*********-IB01-EN-P