7-104 Commissioning and Parameterization <strong>Rexroth</strong> <strong>Indra<strong>Drive</strong></strong><br />

Function<br />

Function<br />

Function<br />

Note: If you make an attempt of phase progression without the drive<br />

having been rebooted, either a switching command error will<br />

occur or a system error (F8xxx) entered before the firmware<br />

update will be displayed.<br />

See also Functional Description "MultiMediaCard (MMC)"<br />

P-0-4073, Field bus: diagnostic message<br />

Input min/max: Default value: Unit:<br />

MPB: --- / --- --- --<br />

This parameter contains the status of the field bus status machine in plain<br />

text. The diagnostic messages depends on the field bus used and is<br />

according to the designations used in the standard.<br />

See also Functional Description "PROFIBUS-DP"<br />

P-0-4074, Field bus: data format<br />

Input min/max: Default value: Unit:<br />

MPB: 0 / 1 0 --<br />

Parameter P-0-4074, Field bus: data format describes the arrangement<br />

of 32-bit-values in the telegram (process data channel).<br />

P-0-4074 = 0<br />

P-0-4074 = 1<br />

P-0-4074, Field bus: data format<br />

16-bit low<br />

16-bit high<br />

32-bit values (bus)<br />

See also Functional Description "PROFIBUS-DP"<br />

P-0-4075, Field bus: watchdog<br />

16-bit high<br />

16-bit low<br />

Input min/max: Default value: Unit:<br />

MPB: --- / --- 0 ms<br />

In this parameter the watchdog time transmitted by the master in the<br />

parameterization telegram is stored in ms. If the master communication is<br />

interrupted for more than this time, a communication error is generated.<br />

See also Functional Description "PROFIBUS-DP"<br />

P-0-4076, Field bus: cycle time (Tcyc)<br />

Input min/max: Default value: Unit:<br />

MPB: 500 / 65000 2000 us<br />

DOK-INDRV*-FU*********-IB01-EN-P