7-116 Commissioning and Parameterization <strong>Rexroth</strong> <strong>Indra<strong>Drive</strong></strong><br />
Features of "I/O Mode<br />
Positioning"<br />
Features of "I/O Mode Preset<br />
Velocity"<br />
Features<br />
Real-Time Channel<br />
Note: The respective default settings are activated by selecting the<br />
profile type and subsequent action "load default<br />
communication parameters" (see also P-0-4090 and<br />
S-0-0262).<br />
Specific features of "I/O mode positioning":<br />
• The drive is operated in "positioning block mode, lagless, encoder 1"<br />
(see also "Positioning Block Mode" in chapter "Operating Modes").<br />
• In this operating mode, 64 programmable positioning blocks can be<br />
selected and started via 6 bits (in the 16 bit wide control word).<br />
• The jog function can be activated in P-0-4068, Field bus: control<br />
word IO. "<strong>Drive</strong>-controlled positioning" was set as the 1st secondary<br />
operating mode (see also "<strong>Drive</strong>-Controlled Positioning" in chapter<br />
"Operating Modes").<br />
Specific features of "I/O mode preset velocity":<br />
• The drive is operated in the "velocity control" mode (see also "Velocity<br />
Control" in chapter "Operating Modes").<br />
• In this operating mode you can, for example, select and start<br />
5 programmable fixed velocity command values (in the 16 bit wide<br />
control word) and operate the ramp generator function.<br />
Freely Configurable Mode (<strong>Rexroth</strong> Profile Type)<br />
To use the extensive and numerous functions of a <strong>Rexroth</strong> drive with field<br />
bus interface it is necessary, in addition to the I/O modes, to define<br />
another profile, the freely configurable mode. This implies the use of a<br />
specific control and status word (P-0-4077, Field bus: control word and<br />
P-0-4078, Field bus: status word).<br />
• The structure (content) of the real-time data channel must be defined<br />
via the configuration parameters P-0-4080 and P-0-4081. No profiledependent<br />
settings and checks are carried out!<br />
• In this profile type it is the <strong>Rexroth</strong>-specific definitions for the field bus<br />
control and status words which apply. Some bits in the parameters<br />
P-0-4077, Field bus: control word and P-0-4078, Field bus: status<br />
word can only be used in conjunction with certain operating modes.<br />
• This profile type allows using the entire drive functionalities (e.g.<br />
velocity synchronization, drive-controlled positioning, ...).<br />
• The primary mode of operation and the secondary operating modes<br />
can be freely determined in the parameters S-0-0032, S-0-0033 etc.<br />
• The operating mode "drive-controlled positioning" is set as default<br />
setting with the command values S-0-0282, S-0-0259 and 2x S-0-0000<br />
and the actual values S-0-0386, S-0-0040, S-0-0390 (see also below<br />
"Exemplary Configurations: <strong>Drive</strong>-Controlled Positioning").<br />
Note: The parameter P-0-4077, Field bus control word or<br />
P-0-4078, Field bus status word must always be contained<br />
in the 1 st place in the configuration parameters P-0-4080 and<br />
P-0-4081.<br />
In the real-time channel of the field bus the data configured in P-0-4081,<br />
Field bus: config. list of cyclic command value data ch. and<br />
DOK-INDRV*-FU*********-IB01-EN-P