8-4 Diagnostic and Service Functions <strong>Rexroth</strong> <strong>Indra<strong>Drive</strong></strong><br />

Putting the <strong>Drive</strong> into Operation<br />

<strong>Drive</strong> Behavior<br />

Putting the <strong>Drive</strong> into Operation<br />

The drive can only be put into operation again when:<br />

1. the error reaction has been completed, i.e. the drive has stopped<br />

(v=0!).<br />

2. the error message was cleared by the error clearing command (cf.<br />

S-0-0099, C0500 Reset class 1 diagnostics).<br />

3. the cause of the error was removed.<br />

4. the drive is in the operating mode again and power was switched on<br />

("Ab").<br />

5. drive enable was switched on again (0-1 edge).<br />

Fatal Errors (F8xxx)<br />

Basically there are 2 kinds of fatal errors (F8 errors):<br />

• fatal errors during initialization (initialization errors) (e.g. F8201 and<br />

F8203, F8118, F8120, ...)<br />

• fatal errors during operation (e.g. F8060, F8022, ...)<br />

Note: Fatal initialization errors cannot be cleared, they require the<br />

drive to be switched off completely.<br />

In addition to completely switching off the drive, fatal errors<br />

associated with the safety technology (e.g. F8201 and F8203)<br />

require safety technology to be completely recommissioned.<br />

In the case of fatal errors, closed-loop control (or open-loop U/f control) of<br />

the drive is no longer ensured; with these errors the drive, independent of<br />

the setting in P-0-0119, Best possible deceleration and P-0-0117,<br />

Activation of NC reaction on error, therefore is immediately switched<br />

off, i.e. it goes torque-free (see also Functional Description "Error<br />

Reaction").<br />

Note: In the case of fatal errors, the settings in P-0-0118, Power<br />

supply, configuration still are taken into account.<br />

After a fatal error has occurred, the drive can only be commissioned again<br />

when:<br />

1. the error message was cleared by the error clearing command (cf.<br />

S-0-0099, C0500 Reset class 1 diagnostics) [to do this it might<br />

possibly be necessary to switch to the parameter mode or switch the<br />

drive off completely].<br />

2. the actual cause of the error was recognized and removed. This<br />

might possibly imply the replacement of an entire component (e.g.<br />

motor or drive controller).<br />

3. the drive is in the operating mode again and power was switched on<br />

again ("Ab").<br />

4. drive enable was switched on again (0-1 edge).<br />

Note: In case fatal errors are occurring repeatedly, contact our<br />

service department as operating the drive then is no longer<br />

possible.<br />

DOK-INDRV*-FU*********-IB01-EN-P