7-42 Commissioning and Parameterization <strong>Rexroth</strong> <strong>Indra<strong>Drive</strong></strong><br />

Function<br />

Function<br />

Function<br />

Function<br />

Function<br />

S-0-0106, Current loop proportional gain 1<br />

Input min/max: Default value: Unit:<br />

MPB: 0,00 / 500,00 8,00 V/A<br />

This parameter is used to define the P-gain for the current loop (for the Id<br />

and Iq control loop). Parameterization of the current loop proportional gain<br />

depends on the control performance (current loop clock TA,i) and the<br />

selected switching frequency (cf. P-0-0001).<br />

S-0-0107, Current loop integral action time 1<br />

Input min/max: Default value: Unit:<br />

MPB: 0,0 / 429496729,5 2,0 ms<br />

The value for the current loop integral action time 1 is motor-specific and<br />

is determined individually for each motor type.<br />

S-0-0109, Motor peak current<br />

Input min/max: Default value: Unit:<br />

MPB: 0,000 / 1000,000 5,000 A eff<br />

Maximum allowed current that may temporarily flow in the motor.<br />

See also Functional Description "Limitations"<br />

S-0-0110, Amplifier peak current<br />

Input min/max: Default value: Unit:<br />

MPB: --- / --- --- A eff<br />

Peak current of the controller. The value is set automatically by the<br />

device. This current is only available temporarily.<br />

See also Functional Description "Current Limitation"<br />

S-0-0111, Motor current at standstill<br />

Input min/max: Default value: Unit:<br />

MPB: 0,000 / 500,000 1,000 A eff<br />

The value of this parameter is the torque-/force-generating component of<br />

the continuous motor current when the motor is loaded with the least<br />

allowed cooling type, with the continuous torque ensured at standstill or<br />

with the ensured continuous force (see motor data sheet).<br />

See also Functional Description "<strong>Rexroth</strong> Motors"<br />

S-0-0112, Amplifier nominal current<br />

Input min/max: Default value: Unit:<br />

MPB: --- / --- --- A eff<br />

DOK-INDRV*-FU*********-IB01-EN-P