5-2 Electrical Data <strong>Rexroth</strong> <strong>Indra<strong>Drive</strong></strong><br />

Control Voltage Supply<br />

Designation<br />

24V control voltage supply<br />

Symbol Unit<br />

<strong>HCS02.1</strong>E;<br />

HCS03.1E<br />

Note: The control sections are supplied via the terminal connectors<br />

24V and 0V at the power section (24V supply).<br />

Note: The isolated inputs/outputs at X31 and X32 are not supplied<br />

via the connections of the 24V supply of the power section. A<br />

separate voltage supply is required for these inputs/outputs.<br />

Note: Overvoltage of more than 33 V has to be discharged by<br />

means of the appropriate electrical equipment of the machine<br />

or installation.<br />

This equipment includes:<br />

• 24V power supply units that reduce incoming overvoltages<br />

to the allowed value.<br />

• Overvoltage limiters at the control cabinet input that limit<br />

existing overvoltage to the allowed value. This, too, applies<br />

to long 24V lines that have been run in parallel to power<br />

cables and mains cables and can absorb overvoltages by<br />

inductive or capacitive coupling.<br />

UN3 V • 24 ± 20%<br />

(if no motor holding brake has to be supplied)<br />

• If motor holding brakes are to be supplied, observe<br />

the data of the motor documentation. The following<br />

values are normally sufficient:<br />

24 ± 5% at motor cable length < 50 m<br />

26 ± 5% at motor cable length > 50 m<br />

max. ripple content w - mustn't exceed the control voltage range<br />

max. allowed overvoltage UN3max V 33 (max. 1 ms)<br />

Power consumption of power sections 1)<br />

<strong>HCS02.1</strong>E-W0012 PN3 W 12<br />

<strong>HCS02.1</strong>E-W0028 PN3 W 14<br />

<strong>HCS02.1</strong>E-W0054 PN3 W 23<br />

<strong>HCS02.1</strong>E-W0070 PN3 W 23<br />

HCS03.1E-W0070 PN3 W 23<br />

HCS03.1E-W0100 PN3 W 25<br />

HCS03.1E-W0150 PN3 W 25<br />

HCS03.1E-W0210 PN3 W 30<br />

Power consumption of control sections 2)<br />

CSB01.1N-FC… PN3 W 7,5<br />

CSB01.1N-PB… PN3 W 7,5<br />

Typ. inrush current of control sections<br />