02.02.2013 Views

Rexroth IndraDrive C Drive Controllers HCS02.1 ... - Bosch Rexroth

Rexroth IndraDrive C Drive Controllers HCS02.1 ... - Bosch Rexroth

Rexroth IndraDrive C Drive Controllers HCS02.1 ... - Bosch Rexroth

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Rexroth</strong> <strong>Indra<strong>Drive</strong></strong> Commissioning and Parameterization 7-93<br />

Function<br />

Function<br />

Function<br />

Function<br />

DOK-INDRV*-FU*********-IB01-EN-P<br />

The list parameter "P-0-1208", in conjunction with the parameter<br />

"P-0-1207" (lower limit of velocity masking window), defines four velocity<br />

ranges (velocity windows).<br />

The ranges apply to positive and negative velocities, the definitions of the<br />

ranges are mirrored with regard to speed zero.<br />

Note:<br />

• The function "velocity masking window" is only effective in<br />

the "velocity control" mode.<br />

• The parameter "P-0-1210, Status word of velocity control<br />

mode" contains information on the status of the current<br />

command value with regard to a velocity masking window.<br />

See also Functional Description "Velocity Loop"<br />

P-0-1209, Acceleration factors for velocity masking<br />

window<br />

Input min/max: Default value: Unit:<br />

MPB: 1,00 / 100,00 --- --<br />

The list parameter P-0-1209 contains the acceleration factors that take<br />

effect in the velocity ranges defined with P-0-1207 and P-0-1208.<br />

The ramp generator passes the range of the velocity window (P-0-1207<br />

and P-0-1208). But the acceleration factors indicated in P-0-1209 have a<br />

multiplying effect on the acceleration and deceleration values or, in the<br />

case of alternative scaling of the acceleration, on the ramp times of the<br />

ramp generator (P-0-1201, P-0-1203, P-0-1211 and P-0-1213).<br />

See also Functional Description "Velocity Loop"<br />

P-0-1210, Status word of velocity control mode<br />

Input min/max: Default value: Unit:<br />

MPB: --- / --- --- --<br />

For the velocity control mode the parameter P-0-1210 contains<br />

information on the current status of the ramp generator and the current<br />

command value.<br />

Note: The parameter P-0-1210 can be configured in the cyclic actual<br />

value channel (e.g. AT with SERCOS) in S-0-0144, Signal<br />

status word and assigned to the digital outputs.<br />

See also Functional Description "Velocity Loop"<br />

P-0-1211, Deceleration ramp 1<br />

Input min/max: Default value: Unit:<br />

MPB: 0 S-0-0160<br />

The deceleration entered in P-0-1211, Deceleration ramp 1 only takes<br />

effect in the "velocity control" mode.