<strong>Rexroth</strong> <strong>Indra<strong>Drive</strong></strong> Commissioning and Parameterization 7-85<br />

DOK-INDRV*-FU*********-IB01-EN-P<br />

• improved nat. cooling<br />

• reduced nat. cooling<br />

P-0-0690 – P-0-0899 (Synchronization Mode)<br />

Function<br />

Function<br />

Function<br />

See also Functional Description "Motor, Mechanical Axis System,<br />

Measuring Systems" and "Current and Torque Limitation (Closed-Loop)"<br />

P-0-0690, Additive velocity command value, process<br />

loop<br />

Input min/max: Default value: Unit:<br />

MPB: 0 S-0-0044<br />

In addition to S-0-0037, parameter P-0-0690 is used to set an additive<br />

velocity command value.<br />

Note: P-0-0690 can preferably be used for drive-based process<br />

loops (by means of MLD)!<br />

P-0-0806, Current mains voltage crest value<br />

Input min/max: Default value: Unit:<br />

MPB: --- / --- --- V<br />

This parameter for HCS03 devices (converters) displays the current crest<br />

value of the mains voltage.<br />

P-0-0810, Minimum mains crest value<br />

Input min/max: Default value: Unit:<br />

MPB: 0 / 780 --- V<br />

For HCS converters, in this parameter it is possible to set an individual<br />

minimum value for the crest value of the mains voltage. The value is only<br />

effective, if it is greater than the minimum value of the mains connection<br />

voltage range!<br />

For HCS02<br />

If the mains crest value, when the converter is switched on, is lower than<br />

the value in P-0-0810, the diagnostic message E2814 Undervoltage in<br />

mains is generated.<br />

For HCS03<br />

If the mains crest value, when the converter is switched on or is in<br />

operation, is lower than the value in P-0-0810, the diagnostic message<br />

E2814 Undervoltage in mains is generated.<br />

Note: The mains voltage crest value detected when switching on, for<br />

HCS devices is displayed in P-0-0815, Nominal mains<br />

voltage crest value!