<strong>Rexroth</strong> <strong>Indra<strong>Drive</strong></strong> Commissioning and Parameterization 7-105<br />

Function<br />

Function<br />

Function<br />

Function<br />

DOK-INDRV*-FU*********-IB01-EN-P<br />

The content of P-0-4076, Field bus: cycle time (Tcyc) defines the time<br />

intervals in which the cyclic real-time data (command values and actual<br />

values) are processed in the field bus drive.<br />

See also Functional Description "PROFIBUS-DP"<br />

P-0-4077, Field bus: control word<br />

Input min/max: Default value: Unit:<br />

MPB: --- / --- 0 --<br />

This parameter is used as field bus control word for all BRC profiles such<br />

as "freely configurable mode" (0xFFFE).<br />

Note: The significance and function of the control bits cannot be<br />

configured and is defined by the profile selection!<br />

See also Functional Description "Profile Types - <strong>Rexroth</strong> Profile Types"<br />

P-0-4078, Field bus: status word<br />

Input min/max: Default value: Unit:<br />

MPB: --- / --- 0 --<br />

In the case of field bus drives that are operated in the freely configurable<br />

profile type (P-0-4084 = 0xFFFE), the parameter P-0-4078, Field bus:<br />

status word is used as status word for feedback of the drive status to the<br />

field bus master.<br />

Note: The configuration of P-0-4078, Field bus: status word cannot<br />

be changed, i.e. the bit assignment is fixed and cannot be<br />

parameterized.<br />

See also Functional Description "Supported Profile Types"<br />

P-0-4079, Field bus: baud rate<br />

Input min/max: Default value: Unit:<br />

MPB: --- / --- 0,00 kBaud<br />

Parameter P-0-4079 contains the active baud rate of the field bus<br />

interface. You have to distinguish the following cases:<br />

• PROFIBUS-DP and PROFInet:<br />

The baud rate used by the field bus is automatically determined and<br />

only displayed in this parameter.<br />

• DeviceNet and CanOpen:<br />

The baud rate used by the field bus is set in parameter P-0-4079.<br />

Note: By inputting "0" as baud rate it is possible to activate automatic<br />

baud rate detection. In some cases this however might not<br />

work correctly so that it is recommended to make a manual<br />

input.