501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

1. Design Data, Test Reports: Provide manufacturer test reports indicating product compliance with<br />

requirements.<br />

2. Manufacturer Erection Instructions: Provide manufacturer’s written installation instructions<br />

including proper material storage, material handling, installation sequence, panel location(s), and<br />

attachment methods, details and required trim and accessories.<br />

1.4 QUALITY ASSURANCE<br />

A. Manufacturer Qualifications: Manufacturer shall have a minimum of five (5) years experience in the<br />

production of fire resistive insulated metal wall panels. Manufacturer shall demonstrate past experience<br />

with examples of projects of similar type and exposure.<br />

B. Installer Qualifications: Installer shall be authorized by the manufacturer and the work shall be supervised<br />

by a person having successfully completed a manufacturer training seminar regarding proper installation<br />

of the specified product.<br />

1.5 PANEL PERFORMANCE CRITERIA<br />

A. Use only polyurethane or polyisocyanurate panels produced by the continuous in-line method for optimum<br />

uniformity and quality. Laminated or styrene core panels will not be accepted. Provide metal wall panels<br />

that conform to the following standards:<br />

1. Structural: The design load / deflection criteria and fastening patterns in accordance with ASTM<br />

E72.<br />

a. The deflection criteria shall be L/180 for walls.<br />

2. Air Infiltration: Air leakage shall not exceed 0.001cfm/sq. ft. of wall area at a pressure differential<br />

of 20psf in accordance with ASTM E283.<br />

3. Water Penetration: No uncontrolled water penetration through the panel joints at a pressure<br />

differential of 20psf in accordance with ASTM E331.<br />

4. Methods of Test for Exterior Walls in accordance with AAMA 501-94<br />

5. Thermal Resistance:<br />

a. Panels shall provide nominal thermal resistance of R=7.5 per inch of thickness in<br />

accordance with ASTM C518.<br />

b. Panels shall provide nominal thermal resistance of R=7.2 per inch of thickness in<br />

accordance with ASTM C1363.<br />

6. Fatigue: The panel shall withstand at least 2 million alternate cycles of L/180 deflection without<br />

any evidence of delamination, foam core cracking or permanent deformation.<br />

a. Positive wind pressure and negative wind pressure (suction) are continually bending<br />

interior and exterior composite panels.<br />

7. Freeze / Heat Cycling: Panels shall exhibit no delamination, surface blisters, permanent bowing or<br />

deformation when subjected to cyclic temperature extremes of -20°F (-29°C) to +180°F (+82°C)<br />

temperatures for twenty one (21), eight-hour cycles.<br />

8. Adhesion: Panel adhesion in accordance with ASTM D1623.<br />

INSULATED-CORE METAL WALL PANELS 07413 - 2