501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

structure and piping. The installing contractor, upon substituting an approved alternate,<br />

must submit a computerized duct design showing system pressure requirements and<br />

acoustic data for the complete duct layout.<br />

C. The VAV system, including terminal units, direct digital controls and ATC/Building<br />

Management System shall be furnished by a single manufacturer who shall be responsible<br />

for system performance. If the terminal unit supplier is different from the control system<br />

supplier, then one of the two suppliers must bear sole responsibility for proper system<br />

performance. The supplier bearing responsibility shall be identified at the time of bid.<br />

1.9 WARRANTY<br />

A. Provide manufacturer's parts warranty for one year from unit start-up or eighteen months<br />

from unit shipment, whichever is shorter.<br />

PART 2 - PRODUCTS<br />

2.1 MANUFACTURERS<br />

A. Manufacturer shall participate in the ARI Certification program. Unit performance data<br />

shall be rated in accordance with ARI Standard 880. The manufacturer shall display the<br />

ARI Symbol on all units.<br />

B. Single and dual duct terminal units shall be listed by an independent 3rd party agency as<br />

an entire assembly. Separate Duct Heater agency listing is acceptable if heater is placed<br />

4 feet downstream of the terminal unit. UL and ETL are approved.<br />

C. Fan powered terminal units shall be listed by an independent 3rd party agency as an entire<br />

assembly. Separate Duct Heater agency listing is acceptable if heater is placed 4 feet<br />

downstream of the terminal unit. UL and ETL are approved.<br />

D. Acceptable Manufacturers<br />

2.2 MANUFACTURED UNITS<br />

Trane (Basis of Design)<br />

Price<br />

Titus<br />

A. Fan powered terminal units.<br />

B. Ceiling mounted primary and recirculated air control terminal unit for connection to a single<br />

[medium - 1.5-3.0 in. wg.][high - 4.0-5.0 in. wg.] pressure duct of a central air distribution<br />

system. Controls and reheat coils to be factory installed and tested.<br />

AIR TERMINAL UNITS – VARIABLE VOLUME 15840-3