501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

motor-compressor 5-year warranty temperature control, flexible power cord with 3<br />

pronged grounded plug, 1-1/4" "P" trap with cleanout.<br />

3. Capacity: 8 gallons per hour of 50 F water with room temperature of 90 F and inlet water<br />

temperature of 80 F.<br />

4. Refrigerant: R-134A<br />

5. Size: 23" high, 36-1/4" wide, and 18-5/8" deep.<br />

6. Mounting Height: Mount 38" from upper basin to floor, 32 ½” from lower basin to floor.<br />

7. Compressor: 1/5 HP, 120/1/60.<br />

8. Support: Provide wall bracket.<br />

9. Cabinet Finish: Finish selected by Owner.<br />

U. Emergency Eye/Face Wash – (OAKH-ED1-BZ004, OAKH-EC1-BZ015)<br />

1. Speakman SE-420 Free-Standing Eyesaver, or similar by Haws.<br />

2. Free-standing emergency aerated eye/face wash fixture furnished complete with selfcleaning<br />

and non-clogging, stay-open valve, integral dust shrouds, adjustable volume<br />

control, supply line strainer, aerated eye/face wash with stainless steel bowl, stanchion,<br />

floor flange, all interconnecting fittings, and universal signage.<br />

3. Provide water mixing valve to tepid water control consisting of two independent<br />

thermostatic type with liquid filled sensors. A thermometer shall indicate the leaving<br />

water temperature. It shall have bronze body construction and non-corrosive parts.<br />

4. In the event of hot water failure, the unit will continue to supply cold water at the minimum<br />

required flow. In the event of a cold water failure, the hot water port shall close stopping<br />

all flow.<br />

5. Speakman SE-420 or equal.<br />

V. Emergency Eye/Face Wash-Countertop (OAKH-EC1-BZ020)<br />

1. Speakman SE-572 20 gpm countertop eyesaver, or similar by Haws.<br />

2. Countertop aerated eye/face wash fixture furnished complete with stay-open valve, pull rod,<br />

aerated eye/face wash with stainless steel bowl, hand and all interconnecting fittings.<br />

3. Provide water mixing valve to tepid water control consisting of two independent thermostatic<br />

type with liquid filled sensors. A thermometer shall indicate the leaving water temperature. It<br />

shall have bronze body construction and non-corrosive parts.<br />

4. In the event of a hot water failure, the unit will continue to supply cold water at the minimum<br />

required flow. In the event of a cold water failure, the hot water port shall close stopping all<br />

flow.<br />

PLUMBING FIXTURES AND TRIM 15450-8