501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

e. Visual capable<br />

f. Fusion capable<br />

2.4 LIQUID-FILLED TRANSFORMER SECTIONS<br />

A. Description: Liquid-filled, two-winding, secondary unit substation transformer complying with<br />

IEEE C57.12.00 “Standard General Requirements for Liquid-Immersed Distribution, Power, and Regulating<br />

Transformers” and UL 1062 “Unit Substations”.<br />

B. KVA Rating: 3000 KVA.<br />

C. Voltage: Delta - wye configuration. Input – 12KV; Output – 480/277V, three phase, four wire. (Supplier to<br />

confirm primary voltage of incoming electrical service prior to release of order.)<br />

D. Insulating Liquid: Less flammable, edible-seed-oil based, and listed by a Nationally Recognized Testing<br />

Laboratory acceptable to the authority having jurisdiction as complying with California Electrical Code<br />

requirements for fire point of not less than 300 deg C when tested according to ASTM D 92 “Standard Test<br />

Method for Flash and Fire Points by Cleveland Open Cup Method”. Liquid shall be readily and completely<br />

biodegradable per EPA OPPTS 835.3100 “Aerobic Aquatic Biodegradation” and nontoxic. The fluid shall be<br />

non-bioaccumulating. The fluid shall be Factory Mutual Approved and shall be a UL Classified Transformer<br />

Fluid, Envirotemp FR3 or approved equal.<br />

E. Insulation Temperature Rise: 65 deg C when operated at rated kVA output in a 40 deg C ambient<br />

temperature.<br />

F. Basic Impulse Level: 95 kV.<br />

G. Full-Capacity Voltage Taps: Four nominal 2.5% taps, two above and two below rated primary voltage; with<br />

externally operable tap changer for de-energized use and with position indicator and padlock hasp.<br />

H. Cooling System: Liquid cooled<br />

I. Impedance: 5.75% percent.<br />

J. Copper bus connections for connection to incoming primary switch and secondary distribution section.<br />

K. Accessories: Grounding pads, lifting lugs, and provisions for jacking under base. Transformers shall have<br />

a steel base and frame allowing use of pipe rollers in any direction, and an insulated, low-voltage, neutral<br />

bushing with removable ground strap. Include the following additional accessories:<br />

1. Liquid-level gage.<br />

2. Pressure-vacuum gage.<br />

3. Liquid temperature indicator.<br />

4. Drain and filter valves.<br />

5. Pressure relief device.<br />

2.5 SECONDARY 480/277V SECTIONS<br />

A. Secondary Bus<br />

12 KV – 480/277V SECONDARY DOUBLE-ENDED UNIT SUBSTATIONS 16371-5