501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

C. Access doors shall be Duro Dyne, or similar by Ventfabrics.<br />

2.12 TEST CONNECTIONS<br />

A. Instrument test connections shall be installed in the return air, outside air and supply air ducts of<br />

each air unit.<br />

B. Test connections shall be Ventfabrics #699-2 or equal.<br />

2.13 FLEXIBLE CONNECTIONS<br />

A. Heavy glass fabric double coated with neoprene, 30 oz/sq yd, air tight, water tight, and fire<br />

retardant, complete with all angles, bolts, and clips required to fasten fabric to sheetmetal. Install<br />

between duct and air unit.<br />

B. Flexible connections shall be Ventfabrics "Ventglas" or equal.<br />

2.14 GRILLES, REGISTERS, AND DIFFUSERS<br />

A. Manufacturer shall submit a written guarantee that ceiling diffusers will distribute air<br />

uniformly through the conditioned space with a 20 degree F temperature differential<br />

between average room temperature and supply air temperature.<br />

B. The manufacturer’s representative shall review the drawings and system design prior to<br />

submission of the grille, register, and diffuser submittal.<br />

C. Manufacturer shall guarantee that all grilles, registers, and diffusers furnished will perform as<br />

required for the intended application. Exceptions shall be brought to Engineer's attention prior to<br />

bidding the project.<br />

D. Provide SCHEDULE for approval clearly indicating the room, CFM, size, static pressure drop,<br />

throw and NC level.<br />

NOTE: FAILURE TO PROVIDE TABULATED SCHEDULE WILL RESULT IN THE AUTOMATIC<br />

REJECTION OF SUBMITTAL SCHEDULE SHALL BE AS DELINEATED IN PART 3 -<br />

EXECUTION.<br />

E. Grilles, registers, and diffusers shall be square or rectangular shape unless otherwise noted.<br />

F. Finish shall be white baked enamel unless otherwise noted.<br />

G. Grilles, registers and diffusers in moist locations (lockers, toilet rooms, and janitor closets) shall<br />

have an approved moisture resistant finish, gasketed frames, and aluminum construction.<br />

H. (TYPE A) - Ceiling Diffusers: Fabricated of aluminum having square or rectangular discharge<br />

pattern. Units shall be supplied with overlap margins and square-to-round neck adapter. Center<br />

core shall be fixed pattern, multiple orifice, removable type. Provide with integral, gang-operated<br />

opposed blade damper with removable key operator, operable from face. Finish shall be<br />

manufacturer's standard baked enamel. Anemostat DF or similar by Titus, or Tuttle and Bailey.<br />

AIR DISTRIBUTION 15800-5