501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

E. Application Specific Controllers shall communicate using LonTalk or BACnet MSTP.<br />

2.7 AUXILIARY CONTROL DEVICES<br />

A. Motorized dampers, unless otherwise specified elsewhere, shall be as follows:<br />

1. Damper frames shall be 16 gauge galvanized sheet metal or 1/8" extruded aluminum with<br />

reinforced corner bracing.<br />

2. Damper blades shall not exceed 8" in width or 48" in length. Blades are to be suitable for<br />

medium velocity performance (2,000 fpm). Blades shall be not less than 16 gauge.<br />

3. Damper shaft bearings shall be as recommended by manufacturer for application.<br />

4. All blade edges and top and bottom of the frame shall be provided with compressible<br />

seals. Side seals shall be compressible stainless steel. The blade seals shall provide for<br />

a maximum leakage rate of 10 CFM per square foot at 2.5" w.c. differential pressure.<br />

5. All leakage testing and pressure ratings will be based on AMCA Publication 500.<br />

6. Individual damper sections shall not be larger than 48" x 60". Provide a minimum of one<br />

damper actuator per section.<br />

B. Control dampers shall be parallel or opposed blade types as scheduled on drawings.<br />

C. Electric damper/valve actuators.<br />

1. The actuator shall have electronic overload or digital rotation sensing circuitry to prevent<br />

damage to the actuator throughout the rotation of the actuator.<br />

2. Where shown, for power-failure/safety applications, an internal mechanical, spring return<br />

mechanism shall be built into the actuator housing.<br />

3. All rotary spring return actuators shall be capable of both clockwise or counter clockwise<br />

spring return operation. Linear actuators shall spring return to the retracted position.<br />

4. Proportional actuators shall accept a 0-10 VDC or 0-20 ma control signal and provide a 2-<br />

10 VDC or 4-20 ma operating range.<br />

5. All non-spring return actuators shall have an external manual gear release to allow<br />

manual positioning of the damper when the actuator is not powered. Spring return<br />

actuators with more than 60 in-lb. torque capacity shall have a manual crank for this<br />

purpose.<br />

6. Actuators shall be provided with a conduit fitting and a minimum 1m electrical cable and<br />

shall be pre-wired to eliminate the necessity of opening the actuator housing to make<br />

electrical connections.<br />

7. Actuators shall be Underwriters Laboratories Standard 873 listed.<br />

8. Actuators shall be designed for a minimum of 60,000 full stroke cycles at the actuator's<br />

rated torque.<br />

E. Binary Temperature Devices<br />

1. Low-Voltage Space Thermostats shall be 24 V, bimetal-operated, mercury-switch type,<br />

with either adjustable or fixed anticipation heater, concealed set point adjustment, 55°F-<br />

85°F set point range, 2°F maximum differential, and vented cover.<br />

2. Line-Voltage Space Thermostats shall be bimetal-actuated, open-contact type or bellowsactuated,<br />

enclosed, snap-switch type or equivalent solid-state type, with heat anticipator,<br />

UL listing for electrical rating, concealed set point adjustment, 55°F-85°F set point range,<br />

2°F maximum differential, and vented cover.<br />

DIRECT DIGITAL CONTROL SYSTEM 15900-11