501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

B. Sprinkler heads shall be Star Model E (Model M for dry pendent heads), or equal, with<br />

temperature ratings and discharge characteristics as scheduled on the drawings.<br />

C. In office areas, sprinkler heads shall be chrome plated with chrome plated escutcheons.<br />

Sprinkler heads in suspended acoustical tile ceilings shall be Model GFR/F2 recessed type<br />

escutcheons as manufactured by Reliable.<br />

D. Provide and install sprinkler emergency cabinets for the storage of spare sprinkler heads. The<br />

cabinets shall be located at each sprinkler riser. Provide necessary wrenches in the cabinet for<br />

use in removal and installation of the sprinklers. The extra sprinkler heads shall be of the same<br />

type and temperature ratings as those installed in the building. Installing of the cabinet and<br />

quantity of spare heads shall be in accordance with NFPA-13, Section 3-2.9.<br />

E. Temperature rating of sprinkler heads near unit heaters or other heat producing objects shall be<br />

in accordance with NFPA-13 Section 5-3.1.4.<br />

F. Sprinkler heads shall be centered in suspended acoustical tile ceiling.<br />

2.9 WATER MOTOR ALARM<br />

A. The water motor alarm(s) shall annunciate system water flow.<br />

B. Each riser shall be provided with a minimum of one water motor alarm Star Model "CD", Viking<br />

Model F-1 or equal.<br />

C. The water motor alarm may serve more than one system, but the piping shall be arranged so<br />

there will be no backflow to activate devices on systems where no flow is occurring.<br />

2.10 FLOW SWITCH<br />

A. Flow switch(es) for Wet Pipe Systems shall be Simplex WF-5, Series 2097 Type VSR-D or<br />

equal. Flow switch shall be UL listed and FM approved.<br />

2.11 FIRE DEPARTMENT CONNECTION (SIAMESE CONNECTION)<br />

A. Fire department connection(s) shall be constructed of cast iron body with brass seals and<br />

checks. Finish shall be polished chrome. Connection shall have two 2-1/2" brass inlet swivel<br />

hose connections with chains and caps and a 4" outlet connection arranged in the same plane<br />

(straightway) pattern, or as otherwise required by the contractor’s hydraulic design. Threaded<br />

connections shall be suitable to local fire department threads. Connection shall be FM, UL<br />

approved. Auto. Spkr., Fire Department Connection shall be cast in raised letters on the plate.<br />

Provide Stortz connection if required by local fire department.<br />

B. Interconnect all installed fire department connections so that fire department truck connection to<br />

any individual siamese connection will pressurize all riser assemblies.<br />

C. The fire department connection shall be Model B as manufactured by Reliable, Star, Viking or<br />

equal.<br />

2.12 TAMPER SWITCH (SUPERVISORY SWITCH)<br />

FIRE PROTECTION 15550-6