501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

2.9 FACTORY TESTS<br />

A. Perform routine tests according to standards specified for components.<br />

B. Conduct transformer tests according to IEEE C57.12.90 “Standard Test Code for Liquid-Immersed<br />

Distribution, Power, and Regulating Transformers” . Perform the following factory-certified tests on each<br />

secondary unit substation:<br />

1. Resistance measurements of all windings on the rated voltage connection and on tap extreme<br />

connections.<br />

2. Ratios on the rated voltage connection and on tap extreme connections.<br />

3. Polarity and phase relation on the rated voltage connection.<br />

4. No-load loss at rated voltage on the rated voltage connection.<br />

5. Exciting current at rated voltage on the rated voltage connection.<br />

6. Impedance and load loss at rated current on the rated voltage connection and on tap extreme<br />

connections.<br />

7. Applied potential.<br />

C. At a minimum, conduct the following factory tests on the 480/277V switchboard in accordance with ANSI<br />

standards:<br />

1. Overpotential test on each bus section<br />

2. Insulation resistance tests<br />

3. Control power wiring verification<br />

4. Instrumentation wiring verification<br />

5. Mechanical operation of all moving components<br />

6. Electrical operation and sequential testing of all control and metering components, to verify all control<br />

system component operation and configuration of all adjustable setpoints and parameters to default<br />

operating conditions<br />

2.10 SPARE PARTS<br />

A. Furnish spare parts described below that match products installed and that are packaged with protective<br />

covering for storage and identified with labels describing contents.<br />

1. Fuses: Minimum of three for each type of fuse used<br />

2. Indicator lamps: Minimum of ten for each type of lamp used<br />

12 KV – 480/277V SECONDARY DOUBLE-ENDED UNIT SUBSTATIONS 16371-10