501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

SECTION 16600 - DIGITAL, ADDRESSABLE FIRE-ALARM AND DETECTION SYSTEM<br />

PART 1 - GENERAL<br />

1.1 SUMMARY<br />

A. This Section describes electrical work for the Fire Alarm and Detection System. Design, provide and<br />

install a new digital addressable fire alarm and detection system for the new Sort Building.<br />

B. Work required under this Section is to be delivered via design/build methodology. This specification shall<br />

be the basis for the design/build package. As such the successful design/build contractor shall become<br />

the engineer of record for the Fire Alarm and Detection System and shall design, supply, install, test and<br />

certify the new, expanded and modified Fire Alarm and Detection System(s). The completed Fire Alarm<br />

and Detection System(s) shall comply with the minimum requirements of all applicable Codes and<br />

Authorities Having Jurisdiction. When applicable Codes, standards or guidelines are in conflict, the most<br />

stringent shall govern<br />

C. The Fire Alarm and Detection System Contractor shall design all necessary modifications to the existing<br />

Fed Ex airport hub’s Fire Alarm and Detection System in order to integrate communications and remote<br />

annunciation into one comprehensive system. The Fed Ex airport hub’s fire alarm remote annunciator is<br />

located in the Security Screening Building lobby. The Fire Alarm and Detection System Contractor shall<br />

obtain any available record drawings of existing Fire Alarm and Detection System equipment from the<br />

Owner (including the systems for the Security Screening Building, the Generator Building, and the<br />

Metroplex Renovations) and conduct a complete site survey to verify the extent and status of the existing<br />

system. Any Fire Alarm and Detection System equipment shown on the drawings in these Contract<br />

Documents is for reference only and is not intended to depict the full extent of the existing system nor are<br />

the drawings intended to depict the entirety of work required under this Section.<br />

D. The general contractor will obtain a conditional permit, conditional upon the timely submission of Fire<br />

Alarm and Detection System drawings and associated documentation. The Fire Alarm and Detection<br />

System Contractor shall prepare working drawings of the Fire Alarm and Detection System for the general<br />

contractor’s building permit application. The schedule for delivery of these drawings shall be coordinated<br />

with the general contractor so as to not delay the building permit process.<br />

E. The Fire Alarm and Detection System Contractor shall determine the requirements applicable to the<br />

submittal of drawings for building permit application from the local Fire Marshal and all other Authorities<br />

Having Jurisdiction and prepare the drawings accordingly. If the local Authorities require that the<br />

submitted drawings be signed and sealed by a licensed professional engineer, then the Fire Alarm and<br />

Detection System Contractor shall provide drawings that are signed and sealed by a licensed professional<br />

engineer in the state of California. If the local Authorities do not require that the submitted drawings be<br />

signed and sealed by a licensed professional engineer, then as a minimum the drawings shall be prepared<br />

by an individual who has attained NICET (National Institute for Certification in Engineering Technologies)<br />

Level III or higher certification in Fire Alarm and Detection Systems. All corresponding submittals and<br />

drawings shall be approved, initialed and show the NICET certification number of the individual<br />

maintaining the certification and taking responsibility for the documentation.<br />

F. <strong>Construction</strong> documents shall include, but not be limited to, all of the following:<br />

1. A floor plan<br />

DIGITAL, ADDRESSABLE FIRE-ALARM AND DETECTION SYSTEM 16600- 1