501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

2.6 FANS – VARIABLE SPEED SUPPLY - AND EXHAUST<br />

A. Provide forward curved supply and exhaust fans with fixed-pitch sheave drive assemblies.<br />

Dynamically balance all fans and the unit's running fan assembly (fan mounted on actual<br />

shaft, bearings and in scroll housing) to assure smooth operation of the fan and it's<br />

associated assembly. Balancing of the fan only shall not be acceptable.<br />

B. Provide forward curved supply and airfoil return fans with fixed-pitch sheave drive<br />

assemblies. Dynamically balance all fans and the unit's running fan assembly (fan<br />

mounted on actual shaft, bearings and in scroll housing) to assure smooth operation of the<br />

fan and it's associated assembly. Balancing of the fan only shall not be acceptable.<br />

C. Mount fan motor(s) and fan on a common base assembly and isolated from unit with 2”<br />

spring isolators. Provide thrust restraint isolation on the fan housing/fan board to assure<br />

smooth fan startup transition and operation.<br />

D. Fan shaft shall be mounted on grease lubricated ball bearings.<br />

E. Motor shall be premium efficiency. Motor shall have a standard T-frame and a minimum<br />

service factor of 1.15. All drive components shall be accessible without the use of<br />

scaffolds or ladders, to facilitate periodic maintenance checks and for operator safety.<br />

2.7 EVAPORATOR COIL SECTION<br />

A. Provide heavy duty aluminum fins mechanically bonded to copper tubes. Evaporator coil<br />

shall be inter- circuited to maintain active coil face area at part load conditions. Coil shall<br />

also utilize internally enhanced tubing for maximum efficiency.<br />

B. Provide a thermostatic expansion valve (TXV) for each refrigerant circuit. Factory pressure<br />

and leak test coil.<br />

C. Provide pitched stainless steel drain pan to assure positive drainage of condensate from<br />

the unit casing.<br />

2.8 AIR-COOLED CONDENSER SECTION<br />

A. Condenser coils shall have all Aluminum Microchannel coils. All coils shall be leak tested<br />

at the factory to ensure pressure integrity. The condenser coil is pressure tested to 650<br />

psig. Subcooling circuit(s) shall be provided as standard.<br />

B. Provide a baked phenolic resin corrosion-protective coating on the condenser coils and<br />

fins.<br />

C. Provide subcooling circuit(s) integral with condenser coils to maximize efficiency and<br />

prevent premature flashing of liquid refrigerant, to a gaseous state, ahead of the<br />

expansion valve.<br />

PACKAGED ROOFTOP AIR CONDITIONING UNITS 15733-6