501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

3. Potential transformers shall be supplied through current-limiting fuses.<br />

2.8 CONTROL SYSTEMS<br />

A. Control circuits: 120 volts, supplied through secondary disconnecting devices from control power transformer.<br />

B. Control power sources for electrically operated circuit breakers: Control power transformers, with interlocking<br />

relays, connected to the line side of each main circuit breaker. Provide 120 volt secondaries connected<br />

through automatic transfer relays to ensure a fail-safe automatic transfer scheme that will prevent the two<br />

power sources from being concurrently connected to the control system and from being connected together.<br />

C. Control Power Fuses: Primary and secondary fuses for current-limiting and overload protection of transformer<br />

and fuses for protection of control circuits.<br />

D. Control Wiring: Factory-installed, with bundling, lacing, and protection included. Provide flexible conductors<br />

for No. 8 AWG and smaller, for conductors across hinges, and for conductors for interconnections between<br />

shipping units.<br />

E. For each electrically operated circuit breaker, provide circuit breaker electrical trip lockout with amber LED<br />

light indication.<br />

F. For each electrically operated circuit breaker, provide LED opened and closed indicators.<br />

G. Automatic Source Transfer Control System<br />

1. The substation shall be provided with an automatic/manual control system that shall provide for control of<br />

the two main circuit breakers and the tie circuit breaker in order to provide an open transition control<br />

sequence for providing power through the switchboard in the event of a loss of either of the main power<br />

sources. Interlocks shall be in place to ensure that under no circumstances can both main breakers and<br />

the tie breaker be closed concurrently.<br />

2. The automatic source transfer control system shall NOT require an uninterruptible power supply for proper<br />

operation.<br />

3. Provide an industrial grade type 27/47 relay to monitor each incoming power source on the line side of the<br />

main circuit breaker.<br />

a. 27/47 relay for undervoltage, phase reversal, single phase and phase voltage balance<br />

b. Undervoltage sensing (device 27) on both sources shall be set at 88% of nominal voltage<br />

(adjustable) with local LED indication.<br />

c. Phase loss (device 47) set at 68% of nominal voltage (adjustable) with local LED indication.<br />

d. Phase sequence (reverse phase) sensing (device 47) set at 2 cycles (adjustable) with local LED<br />

indication.<br />

e. Phase imbalance (device 47) set at 10% (adjustable) with local LED indication<br />

4. Provide a key-operated test switch (located behind the exterior door) for simulating loss of voltage of<br />

either source.<br />

12 KV – 480/277V SECONDARY DOUBLE-ENDED UNIT SUBSTATIONS 16371-8