501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

PART 2 - PRODUCTS<br />

2.1 GENERAL<br />

A. All equipment shall be UL listed and FM approved for its intended use.<br />

2.2 PIPE AND FITTINGS<br />

A. All fire protection piping, valves, fittings, installation, etc. shall conform to NFPA Chapter 13,<br />

Underwriters' Laboratories, and the Owner's insuring company requirements. Pipe and fittings<br />

shall be as follows:<br />

System Location Pipe<br />

Fittings<br />

Wet Ceiling ASTM A135 Sch. 40 Threaded Black Cast<br />

Or ASTM A135 Iron or Plain End, Hole Cut,<br />

Sch. 10 Black Steel Type Fittings or Grooved<br />

Type Victaulic Fittings<br />

B. All fire protection piping shall be UL listed and FM approved for its intended use.<br />

C. Galvanized pipe shall be hot dip galvanized in accordance with ASTM A123.<br />

D. Materials exposed to weathering shall be galvanized.<br />

E. Provide flushing connection at the end of each main consisting of capped nipple 4" long.<br />

2.3 WELD-O-LETS, THREAD-O-LETS<br />

A. "Weld-O-Let," "Thread-O-Let," and other similar type fittings shall be the rounded entry type fittings<br />

as manufactured by Bonney Forge.<br />

2.4 PLAIN END FITTINGS<br />

A. Fittings such as Victaulic "Hooker" and "FIT", products for hole cut pipe, plain end steel pipe<br />

products, snap-let outlets, strapless outlets and other non-grooved products, etc. may be used.<br />

2.5 GROOVED FITTINGS<br />

A. Use “Zero-Flex” Style 07 rigid couplings with EPDM gaskets on wet pipe systems. Pipe ends,<br />

fittings, and gaskets shall be prepared, cleaned, lubricated and installed in strict accordance to the<br />

manufacturer's recommendations. Fittings and housings installed on galvanized piping shall also<br />

be galvanized. Fittings shall be UL/FM approved for fire protection service.<br />

B. All products (fittings, housings, gaskets, etc.) shall be of the same manufacturer.<br />

C. Fittings, couplings, gaskets, etc. shall be as manufactured by the Victaulic Company of America.<br />

2.6 PIPE SUPPORTS<br />

A. Refer to Section 15050, BASIC MATERIALS AND METHODS.<br />

FIRE PROTECTION 15550-4