501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

F. Any service connected to the system which cannot assume test pressures shall be disconnected<br />

and protected from damage and individually tested. In no case shall any part of the systems be<br />

obscured from testing.<br />

G. A written report of all tests shall be forwarded to the Engineer after completion of the test. The<br />

report shall include the original signature of the witnessing authorized representative of the Owner<br />

acknowledging the completion of the test. A copy of the test report shall be included within the<br />

Operating and Maintenance Manuals. NFPA Test Report Form shall be utilized.<br />

H. All additional tests as required by NFPA, the Owner's insuring agency, local or state authorities,<br />

etc., shall be performed as required by the Contractor. A written report and formal acceptance<br />

certificates shall be included within the Operating and Maintenance Manuals.<br />

I. All tests shall be performed under constant supervision with the authority to bleed off excess<br />

pressure that may develop. No test shall remain on work unless continuously attended.<br />

J. The Contractor and his subcontractors shall final test the entire system, including all electrical work<br />

and alarm panels, in the presence of the Engineer and the Owner's representative. It shall be the<br />

responsibility of the Contractor to coordinate the testing and contact all parties involved. Testing<br />

shall be completed using a contractor prepared and prior approved list of Actions and<br />

Observations. This list shall be used as troubleshooting guide only and does not constitute the<br />

sole basis for system acceptance. The Contractor shall sequentially perform the items listed in the<br />

Action Column and record the results in the Observation Column. If any unusual observations are<br />

noted, troubleshooting will not be started until all items in the Action Column are investigated. All<br />

items shall be corrected and the entire testing procedure shall be repeated until no unusual<br />

observations are noted. A written report of this test shall be forwarded to the Engineer for review<br />

and included within the Operational and Maintenance Manuals.<br />

3.5 CERTIFICATE OF ACCEPTANCE<br />

A. The Contractor shall furnish a certificate to the Owner of final inspection and acceptance by the<br />

Owner's insuring agency and local governing authorities after the work covered by this Section is<br />

completed.<br />

3.6 RECORD DRAWINGS<br />

A. Maintain two sets of Contract documents; i.e., drawings (including Owner's insuring agency<br />

approved drawings), specifications, addenda, modifications, and shop drawings at the site in good<br />

order, and annotated daily to show all changes made during the construction process. At the<br />

conclusion of the project, verify the accuracy of these drawings and stamp each drawing “record”<br />

with a stamp indicating the contractor’s name, date and the signature of a principal of the<br />

company. Deliver one set to the Owner and one set to the Engineer. Also provide one set of all<br />

drawings in electronic AutoCad 2010 format to the Engineer.<br />

B. One set of stamped "record" record drawings and calculations shall be placed in each operating<br />

and maintenance manual.<br />

3.7 KEY PLANS<br />

A. Key Plans of building zoning shall be furnished by the Contractor. These Key Plans shall indicate<br />

service utility entrances, riser locations, riser numbers, building areas served for sprinklered Fed<br />

Ex facilities at this site, types of systems, alarm panel locations, valve locations and control<br />

FIRE PROTECTION 15550-10