501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

D. Provide vertical discharge, direct drive fans with steel blades, and three phase motors.<br />

Fans shall be statically and dynamically balanced. Motors shall be permanently lubricated,<br />

with built-in current and thermal overload protection and weathertight slinger over motor<br />

bearings.<br />

E. Provide factory-installed louvered steel coil guards around perimeter of condensing<br />

section to protect the condenser coils, refrigerant piping and control components.<br />

Louvered panels shall be fabricated from heavy gauge galvanized steel and be rigid<br />

enough to provide permanent protection for shipping and pre-/post- installation. Course<br />

wire mesh is not an acceptable material for coil guards.<br />

F. Condenser coils shall be V-banked for cleaning ease. The coils shall not exceed 14 fins<br />

per inch density in order to permit routine cleaning, and prevent excessive air pressure<br />

drop across the condenser coil.<br />

2.9 REFRIGERATION SYSTEM<br />

A. Compressor: shall be industrial grade, energy efficient direct drive 3600 RPM maximum<br />

speed reciprocating or scroll type. The motor shall of a suction gas cooled hermetic<br />

design. Compressor shall have centrifugal oil pump with dirt separator, oil sight glass, and<br />

oil charging valve.<br />

B. If semi-hermetic reciprocating industrial grade compressors are utilized provide single<br />

piece crankshafts, connecting rods aluminum pistons, rings to prevent gas leakage, high<br />

strength non-flexing ring type suction and discharge valves, spring loaded heads,<br />

replaceable cylinder liners, and sealing service immersed in oil. Provide removable<br />

discharge heads and hand hole covers, and discharge service valves.<br />

C. Provide with thermostatic motor winding temperature control to protect against excessive<br />

motor temperatures resulting from over-/under-voltage or loss of charge. Provide high and<br />

low pressure cutouts, and reset relay.<br />

D. Provide factory-installed compressor lockout thermostat to prevent compressor operation<br />

at low ambient conditions.<br />

E. Provide coil frost protection compressor unloading based on refrigerant circuit suction<br />

temperature to prevent coil frosting with minimum energy usage. As an alternate, factoryinstalled<br />

hot gas bypass shall be required on all VAV units to prevent coil frosting.<br />

2.10 EXHAUST/RETURN SECTION<br />

A. 100 Percent Modulating Return Fan single width plenum fan with airfoil blade shall be<br />

mounted on a shaft with fixed sheave drive. The fan shall be dynamically balanced for the<br />

operating envelop and tested in factory before being installed in unit. The plenum fan shall<br />

be test run in unit as part of unit test. Fan operating envelope rpm shall be below first<br />

critical speed. Fan shaft shall be mounted on two grease lubricated ball or roller bearings<br />

designed for 200,000-hour average life. Extended grease lines shall be provided to allow<br />

PACKAGED ROOFTOP AIR CONDITIONING UNITS 15733-7