501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

1. The secondary bus bars shall be tin-plated copper. Main horizontal bus bars shall be mounted with all<br />

three phases arranged in the same vertical plane. Bus sizing shall be based on ANSI standard<br />

temperature rise criteria of 65 degrees C over a 40 degrees C ambient (outside the enclosure).<br />

2. Provide a full capacity neutral bus.<br />

3. A copper ground bus shall be furnished firmly secured to each vertical section structure and shall<br />

extend the entire length of the switchgear. The ground bus short-time withstand rating shall meet that<br />

of the largest circuit breaker within the assembly.<br />

B. Wiring/Terminations<br />

1. Small wiring, necessary fuse blocks and terminal blocks within the switchgear shall be furnished as<br />

required. Control components mounted within the assembly shall be suitably marked for identification<br />

corresponding to the appropriate designations on manufacturer’s wiring diagrams.<br />

2. Provide a front accessible, isolated vertical wireway for routing of factory and field wiring. Factory<br />

provisions shall be made for securing field wiring without the need for adhesive wire anchors.<br />

3. Front access to all circuit breaker secondary connection points shall be provided for ease of<br />

troubleshooting and connection to external field connections without the need of removing the circuit<br />

breaker for access.<br />

4. Lugs shall be provided in the incoming line section for connection of the main grounding conductor.<br />

Additional lugs for connection of other grounding conductors shall be provided as indicated on the<br />

drawings.<br />

C. Main and Tie Circuit Breakers<br />

1. Main and tie circuit breakers shall be drawout type, electrically operated. All closing shall be<br />

electrically supervised. The main and tie circuit breakers shall NOT have any means to manually close<br />

that would bypass the electrical interlocks. Under no conditions shall both main breakers and the tie<br />

breaker be closed concurrently. Manual closing shall be possible only through a control switch that<br />

acts on the electrical operator.<br />

2. The case of the circuit breaker shall be a polyester thermoset material providing high dielectric<br />

strength.<br />

3. All circuit breaker operating mechanisms are to be two-step, fully-stored energy devices for quickmake,<br />

quick-break operation with a maximum of a five-cycle closing time. Open-close-open cycle shall<br />

be possible without recharging. Motor operator shall automatically charge when circuit breaker is<br />

closed.<br />

4. Current-carrying components shall be completely isolated from the accessory mounting area and<br />

double insulated from the operator with accessory cover in place.<br />

5. Padlocking provisions shall be furnished to receive up to three padlocks when circuit breaker is in the<br />

disconnected position, positively preventing unauthorized closing of the circuit breaker contacts.<br />

12 KV – 480/277V SECONDARY DOUBLE-ENDED UNIT SUBSTATIONS 16371-6