04.01.2013 Views

TranSystems Corporation - LGM Construction

TranSystems Corporation - LGM Construction

TranSystems Corporation - LGM Construction

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

6. Data shall be shared between networked System Controllers.<br />

7. The System Controller shall utilize industry recognized open standard protocols for<br />

communication to unit controllers.<br />

8. The System Controller shall continually check the status of its processor and memory<br />

circuits. If an abnormal operation is detected, the controller shall:<br />

a) Assume a predetermined failure mode.<br />

b) Generate an alarm notification.<br />

c) Create a retrievable file of the state of all applicable memory locations at the time of the<br />

failure.<br />

d) Automatically reset the System Controller to return to a normal operating mode.<br />

B. Communications. Each System Controller shall reside on the Enterprise wide network, which is<br />

same high-speed network as the workstations. The Enterprise wide network will be provided by<br />

the owner and supports the Internet Protocol (IP). Local connections of the System Controller shall<br />

be on ISO 8802-3 (Ethernet). Each System Controller shall also perform routing to a network of<br />

Custom Application and Application Specific Controllers) [Optional – Each System Controller shall<br />

perform communications to a network of Custom Application and Application Specific Controllers<br />

using LonTalk FTT-10 and LonMark profiles and/or use BACnet MSTP as prescribed by the<br />

BACnet standard to perform communications to a network of Custom Application and Application<br />

Specific Controllers.<br />

C. Serviceability. Provide diagnostic LEDs for power, communications, and processor. The System<br />

Controller shall have a display on the main board that indicates the current operating mode of the<br />

controller. All wiring connections shall be made to field removable, modular terminal connectors.<br />

The System controller shall utilize standard DIN mounting methods for installation and<br />

replacement.<br />

D. Memory. The System Controller shall maintain all BIOS and programming information indefinitely<br />

without power to the System controller<br />

2.6 APPLICATION SPECIFIC CONTROLLERS<br />

A. General. Application specific controllers (ASC) are microprocessor-based DDC controllers, which<br />

through hardware or firmware design are dedicated to control a specific piece of equipment. They<br />

are not fully user programmable, but are customized for operation within the confines of the<br />

equipment they are designed to serve.<br />

1. Each ASC shall be capable of stand-alone operation and shall continue to provide control<br />

functions without being connected to the network.<br />

2. Each ASC will contain sufficient I/O capacity to control the target system.<br />

B. Serviceability. Provide diagnostic LEDs for power and communications. All wiring connections<br />

shall be clearly labeled and made to be field removable.<br />

C. Memory. The Application Specific Controller shall maintain all BIOS and programming information<br />

in the event of a power loss for at least 90 days.<br />

D. Transformer. Power supply for the ASC must be rated at minimum of 125% of ASC power<br />

consumption, and shall be fused or current limiting type.<br />

DIRECT DIGITAL CONTROL SYSTEM 15900-10