501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

1. The RTU will enable cooling or heating to maintain discharge air temperature setpoint<br />

(adj). The RTU will control the supply fan VFD to maintain duct static pressure setpoint<br />

(adj). The outdoor air damper will open to the minimum setpoint.<br />

E. Discharge Air Temperature Reset Control:<br />

1. The discharge air temperature setpoint, adjustable (55°F-65°F), will be reset based on<br />

either the outside air temperature or zone average temperature. The minimum discharge<br />

air setpoint will be set at 55ºF (adj). The discharge temperature sensor will prevent the<br />

discharge air temperature from falling below the minimum discharge air setpoint (adj). If<br />

the discharge air temperature continues to fall, the discharge temperature sensor will act<br />

as a low discharge temperature limit, a low temperature alarm will be annunciated, and<br />

the unit will shut down. If the discharge temperature rises above the high limit setpoint<br />

the sensor will act as a high discharge temperature limit and will keep the unit running, a<br />

high temperature alarm will be annunciated.<br />

a) Outdoor Air Temperature Reset:<br />

The discharge air temperature setpoint will be adjusted based on the outside air<br />

temperature and the cooling load of the building.<br />

b) Zone Temperature Reset:<br />

The discharge air temperature setpoint will be adjusted based on the<br />

temperature of the critical zone(s).<br />

F. Discharge Duct Static Pressure Control:<br />

1. Reference Duct Static Pressure Optimization in section 4.01 “ROOFTOP/VAV SYSTEM<br />

CONTROL”<br />

G. Economizer Control:<br />

1. The mixed air sensor will measures the dry bulb temperature of the air leaving the<br />

evaporator coil while economizing. When economizing is enabled and the unit is<br />

operating in the cooling mode, the economizer damper is modulated between its<br />

minimum position and 100% to maintain the zone temperature at the economizer<br />

setpoint. The economizer setpoint is (ESP) derived from the cooling and heating setpoints<br />

(CSP and HSP) so that ESP is the higher of CSP – 1.5°f or HSP + 1.5°f. If the mixed air<br />

temperature starts to fall below 53°F, the economizer starts to close, at 50°F, the damper<br />

will be at minimum position. Compressors will be delayed from operating until the<br />

economizer has opened to 100% for 5 minutes.<br />

H. Supply Fan Operation:<br />

a) Reference Dry Bulb:<br />

Outside air (OA) temperature is compared with a reference dry bulb point. The<br />

economizer is enabled when OA temperature is less than reference dry bulb<br />

point. The economizer is disabled when OA temperature is greater than<br />

reference dry bulb point + 5.0°F.<br />

1. The supply fan will be enabled while in the occupied mode and cycled on during the<br />

unoccupied mode. A differential pressure switch will monitor the differential pressure<br />

across the fan. If the switch does not open within 40 seconds after a request for fan<br />

DIRECT DIGITAL CONTROL SYSTEM 15900-23