501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

2.18 TREATED WOOD BLOCKING<br />

A. Treated wood blocking shall be Southern Pine, kiln dried to a maximum moisture content of 19%<br />

(after treatment), and shall be pressure impregnated with chromated copper arsenate (CCA) at the<br />

rate of .40 lbs/C.F. Process shall be Wolmanized (CCA) as manufactured by The Koppers<br />

Company, Inc., Pittsburgh, PA, or equal. Preservatives shall meet AWPA Standard P-5 and<br />

Federal Standard TT-W-550. The treating process and results thereof shall meet Federal Spec.<br />

TT-W-571, AWPA Commodity Standards as applicable, and American Wood Preservers Bureau<br />

Standard LP-22.<br />

2.19 SEALANTS<br />

A. Sealants shall be General Electric <strong>Construction</strong> 1200 Sealant, or equal.<br />

2.20 PAINTING<br />

A. After work is complete, the Contractor shall repaint or touch-up equipment supplied under this<br />

Contract that has become marred during shipment or due to the work of this or any other<br />

Contractor. Touch-up paint shall match original.<br />

2.21 NAMEPLATES<br />

A. Equipment installed under this Contract shall have a permanently attached nameplate<br />

(identification tag) affixed to the equipment. The tag shall be constructed of metal with indented<br />

lettering and attached to the equipment via sheet metal screws or of engraved laminated phenolic<br />

consisting of two outer layers of white phenolic and an inner layer of black engraved to the inner<br />

layer and epoxy cemented to the equipment. Pressure sensitive labels shall not be approved.<br />

The nameplate shall contain the following minimum applicable information: unit identification tag<br />

number, manufacturer, manufacturer's model number, voltage, phase, horsepower, and capacity.<br />

2.22 CONCRETE AND CONCRETE REINFORCEMENT<br />

A. Provide concrete and concrete reinforcement as specified in Division 3.<br />

2.23 EQUIPMENT PADS<br />

A. Provide equipment pads for floor-mounted equipment provided under this Division. Pads shall be<br />

4" high, 2" longer, and 2" wider than the supported equipment. Pads shall be constructed of castin-place<br />

concrete with 6 x 6 10/10 welded wire mesh reinforcing. Edges shall be chamfered unless<br />

otherwise noted. Equipment pads shall be level.<br />

2.24 MISCELLANEOUS STEEL<br />

A. Provide miscellaneous steel shown on the Drawings or required for proper support of equipment or<br />

materials.<br />

2.25 MOTORS<br />

A. Motors 1 HP and up shall have a 1.15 service factor. Motors under 1 HP shall have a 1.25 service<br />

factor. 120V motors 1/6 HP and smaller shall be inherently protected. Minimum motor efficiency,<br />

BASIC MATERIALS AND METHODS 15050-10