501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

a. F-Rating: 1 hour.<br />

b. W-Rating: No leakage of water at completion of water leakage testing.<br />

c. Type of Fill Materials: As required to achieve rating.<br />

H. Firestopping for Miscellaneous Electrical Penetrants:<br />

1. FM Global-Approved Systems: Design No. 204.<br />

a. F-Rating: 1 hour.<br />

b. W-Rating: No leakage of water at completion of water leakage testing.<br />

c. Type of Fill Materials: As required to achieve rating.<br />

I. Firestopping for Miscellaneous Mechanical Penetrants:<br />

1. FM Global-Approved Systems: Design No. 206.<br />

a. F-Rating: 1 hour.<br />

b. W-Rating: No leakage of water at completion of water leakage testing.<br />

c. Type of Fill Materials: As required to achieve rating.<br />

J. Firestopping for Groupings of Penetrants:<br />

1. FM Global-Approved Systems: Design No. 205.<br />

END OF SECTION 07841<br />

a. F-Rating: 1 hour.<br />

b. W-Rating: No leakage of water at completion of water leakage testing.<br />

c. Type of Fill Materials: As required to achieve rating.<br />

THROUGH-PENETRATION FIRESTOPPING 07841 - 8