501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

SECTION 16320 – 12KV CONDUCTORS<br />

PART 1 - GENERAL<br />

The requirements of Section 16010 shall apply to this section except as herein modified.<br />

1.1 SUMMARY<br />

A. This section describes the electrical conductors for the 12KV system.<br />

1.2 SUBMITTALS<br />

A. Product data: For each type of product specified.<br />

1.3 QUALITY ASSURANCE<br />

A. All electrical equipment covered by this specification shall meet all applicable standards of ANSI,<br />

NEMA and IEEE.<br />

B. The service equipment shall meet applicable requirements of the electric service provider. The<br />

facility is located in an area served by the Port of Oakland.<br />

C. Each reel of 15KV cable shall be factory-tested in accordance with ICEA and UL standards. A<br />

certified copy of the factory test is required.<br />

PART 2 - PRODUCTS<br />

2.1 MATERIALS<br />

A. Cable used for the 12KV circuits shall be 15 KV power cable as defined on the drawings. All cable<br />

applied at >600V shall be manufactured by Kerite.<br />

PART 3 - EXECUTION<br />

3.1 INSTALLATION<br />

A. 15KV Cable<br />

1. Where termination, connection or tap hardware is not defined on the drawings,<br />

utilize hardware by Cooper, Elastimold or approved equal that is rated and<br />

intended for the application.<br />

2. After installation, all 15KV cables shall be properly identified by a durable nonmetallic<br />

tag in each manhole. Each tag shall list the feeder identification number<br />

and be secured with plastic tie wraps.<br />

12KV CONDUCTORS 16320-1