501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

2.5 EXIT SIGNS<br />

A. General Requirements for Exit Signs: Comply with UL 924 “Standard for Safety of Emergency Lighting<br />

and Power Equipment” ; for sign colors, visibility, luminance, and lettering size, comply with authorities<br />

having jurisdiction.<br />

2.6 LIGHTING FIXTURE SUPPORT COMPONENTS<br />

A. Comply with Division 16 Section "Hangers and Supports for Electrical Systems" for channel- and angleiron<br />

supports and nonmetallic channel and angle supports.<br />

B. Stem Hangers: 1/2-inch (13-mm) steel tubing with swivel ball fittings and ceiling canopy. Finish same as<br />

fixture.<br />

C. Rod Hangers: 3/16-inch (5-mm) minimum diameter, cadmium-plated, threaded steel rod.<br />

PART 3 - EXECUTION<br />

3.1 INSTALLATION<br />

A. Lighting fixtures: Set level, plumb, and square with ceilings and walls. Install lamps in each fixture.<br />

B. Comply with California Electrical Code for minimum fixture supports.<br />

C. Suspended Lighting Fixture Support:<br />

1. Pendants and Rods: Where longer than 48 inches (1200 mm) , brace to limit swinging.<br />

D. Adjust aimable lighting fixtures to provide required light intensities.<br />

E. Connect wiring according to Division 16 Section "Conductors and Cables."<br />

F. Mark fixtures on the emergency life safety lighting circuits as follows:<br />

1. Office areas – Apply a red paint dot to each fixture in an area that is visible from the office space.<br />

The dot shall be applied with an applicator (not a brush) in order to produce a consistently sized,<br />

neat round dot. “Emergency life safety” lighting fixtures shall include all those that are connected<br />

ahead of all local switching to the life safety generator under normal power failure conditions,<br />

including those fixtures that are connected via a Bodine (or equal) emergency relay control device.<br />

2. Non-office areas – Use a red cover plate for the receptacle or junction box that supplies each<br />

individual fixture. Position the red cover plate so it is visible from the floor below. “Emergency life<br />

safety” lighting fixtures shall include all those that are connected ahead of all local switching to the<br />

life safety generator under normal power failure conditions, including those fixtures that are<br />

connected via a Bodine (or equal) emergency relay control device.<br />

END OF SECTION 16511<br />

INTERIOR LIGHTING 16511 - 3