501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

F. Night Economize Mode [Night Purge Mode]<br />

The AHU shall not be used for Night Heat mode.<br />

1. The BAS time-of-day scheduling application shall support Night Economize functionality.<br />

The Night Economize mode shall be scheduled during the daily block of time when the<br />

outdoor air enthalpy is typically the most effective for economizing.<br />

2. The BAS shall command the VAV Air System to Night economize when all three of the<br />

following conditions are met: temperature of the space is greater than the space’s<br />

occupied cooling setpoint, and the temperature of the space is greater than the Outdoor<br />

Air temperature plus the Minimum Indoor/Outdoor Temperature differential (15 deg F,<br />

adj.), and night economize mode is enabled by the time-of-day schedule.<br />

3. Each VAV box that is associated with the VAS shall control to its occupied cooling<br />

setpoint, and shall modulate box airflow to meet the airflow requirements to cool the<br />

space to the Occupied Cooling setpoint minus the occupied cooling deadband (4 deg F,<br />

adj.).<br />

4. The air handler shall modulate its airflow to maintain the duct static pressure setpoint.<br />

5. Mechanical cooling shall not be used during Night Economize mode.<br />

4.2 DX VAV ROOFTOP UNITS, COOLING ONLY, ECONOMIZER, DDC CONTROLLER (DIRECT DIGITAL<br />

CONTROL)<br />

A. Building Automation System Interface:<br />

1. The Building Automation System (BAS) will send the controller Occupied, Unoccupied,<br />

Optimal Start, Night Heat / Cool, and Timed Override commands. If a BAS is not present,<br />

or communication is lost with the BAS, the controller will operate using its local schedule<br />

and setpoints.<br />

B. Unoccupied Mode:<br />

1. In the unoccupied mode the rooftop unit (RTU) will cycle as required to maintain the<br />

adjustable (adj) unoccupied space heating and cooling setpoints. The variable frequency<br />

drive (VFD) will operate as necessary to maintain duct static pressure setpoint (adj)<br />

during morning warm up or cool down modes. The outside air damper will remain closed,<br />

and the return air damper will remain open during unoccupied mode.<br />

C. Cool-Down Mode:<br />

1. On a transition from the unoccupied mode to occupied mode, if the zone average<br />

temperature is 3°F above the occupied setpoint a morning cool-down mode will be<br />

activated. When morning cool-down is initiated the RTU will enable the fan and DX<br />

cooling or economizer. The outside air damper will remain closed. When the zone<br />

average temperature reaches setpoint (adj), the RTU will transition to the occupied mode.<br />

D. Occupied Mode:<br />

DIRECT DIGITAL CONTROL SYSTEM 15900-22