501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

SECTION 16131 - FACILITY COMMUNICATIONS INFRASTRUCTURE<br />

PART 1 - GENERAL<br />

The Requirements of Section 16010 shall apply to this Section except as herein modified.<br />

1.1 SCOPE<br />

A. This Section describes the electrical work for the facility communications infrastructure.<br />

1.2 RELATED WORK<br />

A. All equipment and wiring for the telephone system, intercom system, computer networking, cable<br />

TV and any other types of facility communications systems will be supplied and installed by the<br />

Owner, unless noted otherwise.<br />

PART 2 - PRODUCTS<br />

2.1 TELEPHONE EQUIPMENT BACKBOARDS<br />

A. Telephone equipment backboards shall be ¾” plywood, painted, sized and located as noted on the<br />

drawings.<br />

2.2 FACILITY COMMUNICATIONS OUTLET BOXES AND CONDUIT SYSTEM<br />

A. Outlet boxes for wall outlets shall be 2-1/2" deep, and ganged where located in close proximity to<br />

other communications outlet boxes or receptacles.<br />

B. Cover all communications wall outlets with blank wall plates. Wall plates shall be the same as<br />

specified for receptacles in Section 16130, only with a blank cover.<br />

C. For each communications outlet box shown or noted on the drawings, supply and install a ¾”<br />

conduit extended up to above the ceiling in finished areas or to the roof steel in unfinished non-<br />

Sort areas, or to a wall location at the perimeter of the Sort equipment area that is accessible by<br />

manlift equipment if outlet box is located in a Sort equipment area. Install an insulated bushing on<br />

each conduit. Install a pull cord into each conduit, as per Section 16130, to facilitate future cable<br />

installation.<br />

PART 3 - EXECUTION<br />

3.2 CLEANING<br />

A. All equipment shall be thoroughly cleaned and left free of dust, dirt, grease, fingerprints, and<br />

accumulated debris. Equipment shall be touched up where scratched with matching paint.<br />

END OF SECTION 16131<br />

FACILITY COMMUNICATIONS INFRASTRUCTURE 16131.1