04.01.2013 Views

TranSystems Corporation - LGM Construction

TranSystems Corporation - LGM Construction

TranSystems Corporation - LGM Construction

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

2. When any VAV damper is more than 75% (adj.) open, the supply fan discharge duct<br />

static pressure setpoint shall be reset upward by 0.1 in W.C. (adj.), at a frequency of 15<br />

minutes (adj.), until no damper is more than 75% open or the static pressure setpoint has<br />

reset upward to the system maximum duct static pressure setpoint or the RTU variablefrequency<br />

drive is at the maximum speed setting.<br />

3. When all VAV dampers are less than 65% (adj.) open, the supply fan discharge duct<br />

static pressure setpoint shall be reset downward by 0.1 in W.C.(adj.), at a frequency of 15<br />

minutes (adj.), until at least one damper is more than 65% open or the static pressure<br />

setpoint has reset downward to the system minimum duct static pressure setpoint or the<br />

RTU variable-frequency drive is at the minimum speed setting.<br />

4. The control bands, setpoint increment values, setpoint decrement values and adjustment<br />

frequencies shall be adjusted to maintain maximum static pressure optimization with<br />

stable system control and maximum comfort control.<br />

5. The BAS shall have the capability to allow the operator to exclude “problem” zones that<br />

should not be considered when determining the optimized setpoint.<br />

6. The BAS shall also read the status of the supply air static pressure sensor and display<br />

the active duct static pressure reading on the status screen.<br />

7. The BAS shall have the ability to identify, and display to the user, the VAV box that<br />

serves the Critical Zone (that is, the zone with the most wide-open VAV damper). This<br />

information shall update dynamically as the location of the Critical Zone changes based<br />

on building load, and duct static pressure setpoint optimization control.<br />

B. Ventilation Optimization<br />

1. The AHU outdoor-air damper shall be controlled to deliver required outdoor airflow at all<br />

load conditions. The outdoor airflow setpoint shall be determined according to ASHRAE<br />

Standard 62.1-2004, Equation 6-8 and Appendix A. The actual outdoor airflow shall be<br />

sensed at the outdoor air intake.<br />

2. The BAS shall include a time-of-day schedule to indicate whether a zone is normally<br />

occupied or unoccupied. When the schedule indicates that the zone is normally<br />

unoccupied, the required outdoor airflow for the zone shall be zero. When the schedule<br />

indicates that the zone is normally occupied, the required outdoor airflow for the zone<br />

shall equal the design outdoor airflow.<br />

3. The required outdoor-air fraction shall be continuously calculated for each VAV terminal<br />

zone. Outdoor-air fraction is defined as the current required outdoor airflow for the zone<br />

divided by the current primary airflow to the zone.<br />

4. The BAS shall regularly determine the highest zone outdoor-air fraction, sum the outdoor<br />

airflow requirements for all VAV zones, and sum the current primary airflows for all VAV<br />

zones to determine the total system primary airflow. This information shall be used in<br />

Equation 6-8 and Appendix A of ASHRAE Standard 62.1-2004 to calculate the minimum<br />

required outdoor airflow for the system. This minimum outdoor airflow setpoint shall be<br />

recalculated every 15 minutes (adj).<br />

DIRECT DIGITAL CONTROL SYSTEM 15900-19

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!