501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

C. Hangers provided for insulated lines shall be sized for the outside diameter of the applied<br />

insulation. Provide temporary wooden blocks, properly sized for the insulation thickness, which<br />

will accurately center the pipe in the hanger and enable the insulation to be applied without<br />

disturbing hanger settings.<br />

D. Black steel hangers and supports shall be protected from corrosion by painting with suitable<br />

coating.<br />

E. Hangers - Insulated Piping - Hangers used with insulated piping shall be sized to accommodate<br />

the pipe and insulation, and shall have a support shield, as specified in SECTION 15250 -<br />

INSULATION, to prevent the hanger from compressing the insulation. Hanger shall be clevis type<br />

with rod and double nuts and washers. Hangers shall be black, Anvil Figure 260, or similar by B-<br />

Line or Michigan Hanger.<br />

F. Hangers - Bare Ferrous Piping - Hangers for bare ferrous pipe shall be the clevis type with rod and<br />

double nuts and washers. Hanger shall be black, Anvil Figure 260, or similar by B-Line or<br />

Michigan Hanger.<br />

G. Hangers - Bare Copper Piping - Hangers for bare copper pipe shall be clevis type with rod and<br />

double nuts and washers, and shall be copper plated. Hanger shall be Anvil Figure CT-65 or<br />

similar by B-Line or Michigan Hanger.<br />

H. Vertical piping shall be supported and laterally braced in intervals not exceeding 15 feet. Support<br />

vertical piping with clamp installed below coupling or hub. Clamp assembly shall be black, Anvil<br />

Figure 138 R (Non-Insulated Ferrous Pipe, 3/8 - 3 inch), black, Anvil Figure 261 (Insulated or Non-<br />

Insulated Ferrous Pipe, 3/4 - 20 inch), copper plated Anvil Figure CT-122 R (Copper Tubing, 1/2 -<br />

2 inch), copper plated Anvil Figure CT-121 (Copper Tubing, 1/2 -4 inch), or similar by B-Line.<br />

2.12 BEAM CLAMPS AND ATTACHMENTS<br />

A. Beam clamps for pipe sizes 3 inch and smaller - Clamps for attachment to I-beam or steel joists<br />

shall be malleable iron C-clamps with hardened steel cup point set screw, locknut and retaining<br />

clip (I-beam clamp). Clamp shall be Grinnell Figure 86 (I-beam clamp), Figure 93 or 94 (steel joist)<br />

or similar by Michigan Hanger.<br />

B. Beam clamps for pipe sizes 4 inch and larger - Clamps for attachment to I-beam or steel joists<br />

shall be malleable iron jaw steel tie rod, nuts and washer. Clamp shall be Grinnell Figure 228,<br />

229, or 292.<br />

C. Fastening devices for material other than steel beams or joists shall be of equal quality and<br />

construction.<br />

D. Provide alternate means of attachment for tube steel building construction.<br />

2.13 SLEEVES<br />

A. Sleeves shall be standard weight galvanized steel pipe with welded anchor lugs.<br />

2.14 ESCUTCHEON PLATES<br />

A. Galvanized escutcheons or plates shall be securely fastened around pipes that are exposed where<br />

they pass through wall, ceilings, or floors.<br />