501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

Internet Protocol (IP). Workstations shall also be able to dial into the system. Fed Ex shall advise<br />

the appropriate language for communication with a main BMS (BACnet or Lon).<br />

Workstation information shall be provided through web pages.<br />

B. Hardware. Each operator workstation shall consist of the following:<br />

1. Personal Computer ,shall have internet explorer 7.0 or higher or Firefox 3.0 or higher<br />

2. Modems. Furnish auto-dial telephone modems and associated cables as required for<br />

communication to remote buildings, and workstations. The modem shall be capable of<br />

transmitting at up to 56K baud, and communicate over voice-grade telephone lines.<br />

C. User Interface<br />

1. Internet Browser. Furnish with either Internet Explorer 7.0 or higher, or Firefox 3.0 or<br />

higher. Java 5.0 or higher must also be installed on the PC.<br />

2. User interface. The system user interface shall be web based graphically orientated.<br />

Provide a method for the operator to easily move between web pages. Dynamic points<br />

shall include analog and binary values, dynamic text, static text, and animation files.<br />

Graphics shall have the ability to show animation of equipment. Animation capabilities<br />

shall include the ability to show a sequence of images reflecting the position of analog<br />

outputs, such as valve or damper positions. Graphics shall be capable of launching other<br />

web pages.<br />

3. Custom background images. Custom background images shall be created with the use of<br />

commonly available graphics packages such as Adobe Photoshop. The graphics<br />

generation package shall create and modify graphics that are saved in industry standard<br />

formats such as GIF and JPEG.<br />

4. Graphics Library. Furnish a library of standard HVAC equipment such as chillers, air<br />

handlers, terminals, fan coils, unit ventilators, rooftop units, and VAV boxes, in 3dimensional<br />

graphic depictions.. The library shall be furnished in a file format compatible<br />

with the graphics generation package program.<br />

5. Engineering Units. Allow for selection of the desired engineering units (i.e. Inch pound or<br />

SI) in the system. Unit selection shall be able to be customized by locality to select the<br />

desired units for each measurement.<br />

D. System Applications. Each system controller shall provide storage of system information. Provide<br />

the following applications at each system controller.<br />

1. Database Save and Restore. A system operator with the proper password clearance<br />

shall be able to archive the database on the designated operator interface PC. The<br />

operator shall also be able to clear a panel database and manually initiate a download of<br />

a specified database to any panel in the system.<br />

2. On-Line Help and Training. Provide a context sensitive, on line help system to assist the<br />

operator in operation and editing of the system. On-line help shall be available for all<br />

system functions and shall provide the relevant data for that particular screen. Additional<br />

help shall be available through the use of hypertext links onscreen.<br />

3. Security. Each operator shall be required to log on to the system with a user name and<br />

password in order to view, edit, add, or delete data. System security shall be selectable<br />

for each operator. The system supervisor shall have the ability to set security levels for<br />

DIRECT DIGITAL CONTROL SYSTEM 15900-6