501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

A. Flexible elastomer sheet insulation shall be a closed cell foamed elastomer having a density range<br />

of 3.0 – 6.0 lbs. per cu.ft., shall have a thermal conductivity of 0.28 BTU-In/Hr-Sq Ft-Deg F at 75<br />

Deg F mean temperature, and shall have a permeability of not greater than 0.08 perm-inches.<br />

B. Insulation shall be AP/Armaflex Sheet and Roll Insulation as manufactured by Armacell.<br />

C. Adhesive for adhering flexible elastomer to sheet metal (outside duct only), and for adhering all<br />

seams and joints shall be rubber based contact adhesive, Armacell 520 or 520 BLV.<br />

2.6 PVC SHEET JACKET<br />

A. All insulation where specified or otherwise shown on the Drawings shall have a jacket of PVC<br />

sheet material. Jacket material shall be 30 mil thick, have a permeability to water vapor of not<br />

greater than .012 perm-in., and be non-toxic, odorless, and resistant to corrosion and exposure.<br />

B. Color of PVC jacket shall be white.<br />

C. Jacket shall be as manufactured by Ceel-Co, or similar by Johns Manville - Zeston, Certain-Teed<br />

or Speed Line Manufacturing Co.<br />

2.7 PVC TAPE<br />

A. PVC tape shall be a 10 mil minimum thickness polyvinyl chloride pressure sensitive tape, 2" in<br />

width, as manufactured by Speed Line, or similar by Proto.<br />

2.8 INSULATION PROTECTION SADDLES AND SHIELDS<br />

A. Insulation protection saddles and shields shall be provided and installed by the Contractor at all<br />

pipe hangers and supports for insulated lines.<br />

B. All insulation protection shields shall be rolled with a true radius to suit the insulation O.D. Prime<br />

galvanized sheet metal shall be used for all shields. The shields shall be sized to wrap the<br />

insulation in an arc between 120 Deg and 180 Deg. The shields shall be anchored to the pipe<br />

insulation with no less than two bands per shield. Bands shall be stainless steel, aluminum, or<br />

galvanized steel matching insulation jackets where applicable.<br />

C. The schedule for the shields shall be as follows:<br />

Pipe Size Shield Gauge<br />

Shield Length<br />

(Inches) (Inches)<br />

2 and smaller 16 8<br />

2-1/2 and 3 14 10<br />

4 14 12<br />

5 and 6 12 14<br />

8, 10, and 12 12 16<br />

D. Pipe insulation saddles shall be fabricated from calcium silicate or high density pre-compressed<br />

fiberglass pipe insulation. Calcium silicate saddles shall not be used on cold water piping systems.<br />

Saddles may be polyisocyanurate or extruded polystyrene where similar materials are specified for<br />

adjoining pipe insulation. Saddle shall be minimally 1/2 section of pipe insulation placed in pipe<br />

INSULATION 15250-3