501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

penetration firestopping and install new materials to produce systems complying with specified<br />

requirements.<br />

3.7 PENETRATION FIRESTOPPING SCHEDULE<br />

A. Where FM Global-approved systems are indicated, they refer to design numbers listed in FM Global's<br />

"Building Materials Approval Guide" under "Wall and Floor Penetration Fire Stops."<br />

B. Firestopping with No Penetrating Items:<br />

1. FM Global-Approved Systems: Design No. 204.<br />

a. F-Rating: 1 hour.<br />

b. W-Rating: No leakage of water at completion of water leakage testing.<br />

c. Type of Fill Materials: As required to achieve rating.<br />

C. Firestopping for Metallic Pipes, Conduit, or Tubing:<br />

1. FM Global-Approved Systems: Design No. 206.<br />

a. F-Rating: 1 hour.<br />

b. W-Rating: No leakage of water at completion of water leakage testing.<br />

c. Type of Fill Materials: As required to achieve rating.<br />

D. Firestopping for Nonmetallic Pipe, Conduit, or Tubing:<br />

1. FM Global-Approved Systems: Design No. 204.<br />

a. F-Rating: 1 hour.<br />

b. W-Rating: No leakage of water at completion of water leakage testing.<br />

c. Type of Fill Materials: As required to achieve rating.<br />

E. Firestopping for Electrical Cables:<br />

1. FM Global-Approved Systems: Design No. 204.<br />

a. F-Rating: 1 hour.<br />

b. W-Rating: No leakage of water at completion of water leakage testing.<br />

c. Type of Fill Materials: As required to achieve rating.<br />

F. Firestopping for Cable Trays with Electric Cables:<br />

1. FM Global-Approved Systems: Design No. 205.<br />

a. F-Rating: 1 hour.<br />

b. W-Rating: No leakage of water at completion of water leakage testing.<br />

c. Type of Fill Materials: As required to achieve rating.<br />

G. Firestopping for Insulated Pipes:<br />

1. FM Global-Approved Systems: Design No. 206.<br />

THROUGH-PENETRATION FIRESTOPPING 07841 - 7