501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

B. Insulation and adhesive materials shall have a flame spread rating of not greater than 25, and a<br />

smoke developed rating of not greater than 50 when tested in accordance with ASTM E-84 or UL-<br />

723 unless noted otherwise.<br />

2.2 INSULATION SPECIFICATION NO. 1 FLEXIBLE ELASTOMER - PIPE<br />

A. Flexible elastomer pipe insulation shall be a closed cell foamed elastomer having a density range<br />

of 3.0 – 6.0 lbs. per cu.ft., shall have a thermal conductivity of 0.27 BTU-In/Hr-Sq Ft - Deg F or<br />

better at 75 deg F mean temperature, and shall have a permeability of not greater than 0.08<br />

perm-inches.<br />

B. Insulation shall be AP/Armaflex SSPipe Insulation as manufactured by Armacell.<br />

C. Fittings, valves, and flanges shall be insulated using field fabricated fitting covers. The material<br />

used shall be identical to the adjacent pipe insulation as specified.<br />

D. Adhesive for adhering all joints in flexible elastomer pipe insulation shall be rubber based contact<br />

adhesive, Armacell 520 or 520 BLV.<br />

2.3 INSULATION SPECIFICATION NO. 2 FIBERGLASS - PIPE<br />

A. Fiberglass pipe insulation shall be one-piece factory molded pipe insulation having a density of not<br />

less than 3.5 lbs. per cu.ft., and having a thermal conductivity of not greater than 0.23 BTU-In/Hr-<br />

Sq Ft - Deg F at 75 Deg F mean temperature. Pipe insulation shall have a factory applied foil and<br />

kraft paper fire retardant, vapor barrier jacket, having a maximum permeance to water vapor of<br />

0.02 perms when tested in accordance with ASTM E96 Procedure A, and a minimum Beach<br />

puncture resistance of 50 when tested in accordance with ASTM D781. Jacket shall have factory<br />

applied self-sealing adhesive lap.<br />

B. Fiberglass pipe insulation shall be Fiberglass 25 ASJ/SSL II as manufactured by Owens-Corning<br />

Fiberglass <strong>Corporation</strong>, or similar by Johns Manville or Knauf.<br />

C. Fittings, valves and flanges shall be insulated using premolded PVC fitting covers. PVC covers<br />

shall be one piece, factory molded, vapor and moisture resistant and shall be Zeston as<br />

manufactured by Johns Manville, or similar by Certain-Teed or Speed Line Manufacturing Co.<br />

Factory furnished fiberglass inserts shall be utilized.<br />

2.4 INSULATION SPECIFICATION NO. 9 FIBERGLASS DUCT WRAP<br />

A. Ducts shall be externally insulated with commercial grade faced duct wrap insulation consisting of<br />

inorganic blankets of glass fibers factory-laminated to a foil reinforced kraft (FRK) vapor barrier<br />

facing. Insulation shall have a thermal conductivity of .25 BTU-In/Hr-Sq Ft-Deg F at 75 Deg mean<br />

temperature when tested in accordance with ASTM C-518, a density of 1.5 lbs/cu ft, and shall<br />

have no accelerating affect on corrosion of aluminum or steel.<br />

B. Insulation shall be All Service faced duct wrap type 150 as manufactured by Owens-Corning<br />

Fiberglas <strong>Corporation</strong>, or similar by Johns Manville, or Certain-Teed.<br />

2.5 INSULATION SPECIFICATION NO. 10 FLEXIBLE ELASTOMER - SHEET<br />

INSULATION 15250-2