501070099 Federal Express Oakland Sort Expansion Issued for Bid 10/11<br />

SECTION 08390 – WATERTIGHT DOORS AND BARRIERS<br />

PART 1 - GENERAL<br />

1.1 RELATED DOCUMENTS<br />

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and<br />

Division 1 Sections of these specifications, apply to this Section.<br />

1.2 SUMMARY<br />

A. Section Includes:<br />

1. Pedestrian Flood Door with frame and hardware.<br />

a. Exterior Pedestrian Doors at the Substation Room.<br />

2. Removable Plank Flood Barrier System<br />

a. Locations as indicated for Overhead Coiling Doors at the Substation Room.<br />

1.3 DESIGN / PERFORMANCE REQUIREMENTS<br />

A. Design watertight doors and planks to perform under hydrostatic loads (and hydrodynamic or other loads<br />

as specified) to control short-term load pressures indicated. All water pressure loads and operating loads<br />

are transferred to the building structure.<br />

B. Standard loading: Standard Flood Doors and Planks are designed for hydrostatic loading, and have no<br />

additional allowances included for hydrodynamic loads, wave loads or debris impact loads.<br />

C. Special loading: Design Flood Doors for hydrodynamic loads, wave loads, debris impact loads, or other<br />

uniform loads as indicated.<br />

D. Design Safety Factor for all watertight door Flood Door and Flood Plank Models of a minimum 2:1. Based<br />

on material ultimate yield strengths.<br />

E. Design Safety Factor for Anchors, minimum of 4:1 for cast-in-place concrete, or minimum of 6:1 for<br />

concrete masonry unit construction.<br />

F. FM Global Approval: Watertight Doors, Plank Systems and assemblies must be pre-approved by FM<br />

Global, designed and installed per FM Approval Class Number 2510 for Flood Abatement Equipment.<br />

1.4 SUBMITTALS<br />

A. Product Data: Manufacturer's data sheets for each type of product indicated including:<br />

WATERTIGHT DOORS AND BARRIERS 08390 - 1