Maharashtra<br />

TRANSMISSION<br />

The transmission system <strong>of</strong> MSEB comprises <strong>of</strong> a very large network consisting <strong>of</strong><br />

132 kV to 400 kV lines and sub-stations as well as a +/- 500 kV, 750 km long, high<br />

voltage direct current (HVDC) transmission line capable <strong>of</strong> transmitting 1,500 MW <strong>of</strong><br />

power. The following table gives the year-wise details <strong>of</strong> number <strong>of</strong> sub-stations,<br />

transformation capacity in MVA, circuit km <strong>of</strong> various voltage levels added in the<br />

period 2001-02 to 2005-06 and proposed expansion <strong>of</strong> the network in future. The<br />

transmission assets <strong>of</strong> MSEB have now been transferred to MSETCL.<br />

Table: Details <strong>of</strong> Transmission System in MSEB/MSETCL<br />

Particulars 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010<br />

-02 -03 -04 -05 -06 -07 -08 -09 -10 -11<br />

No. <strong>of</strong> sub stations<br />

+/- 500 kV 2 2 2 2 2 2 2 2 2 2<br />

400 kV 15 15 16 17 17 18 18 20 23 25<br />

220 kV 106 113 118 120 123 130 145 159 165 171<br />

132 kV and below 301 308 313 322 326 343 358 367 378 387<br />

Total 424 438 449 461 467 493 523 548 568 585<br />

Ckt-km <strong>of</strong> lines<br />

+/- 500 kV 1504 1504 1504 1504 1504 1504 1504 1504 1504 1504<br />

400 kV 6230 6230 6376 6376 6376 6500 6635 7045 8075 8835<br />

220 kV 10399 10872 11288 11415 11512 12072 12504 13415 14656 16060<br />

132 kV and below 14631 14793 14935 15412 15713 16367 17202 18269 19455 20850<br />

Total 32764 33399 34103 34707 35105 36443 37845 40233 43690 47249<br />

MVA capacity <strong>of</strong> sub-stations<br />

+/- 500 kV 3582 3582 3582 3582 3582 3582 3582 3582 3582 3582<br />

400 kV 10090 10720 11535 12035 12035 12350 12665 13610 15500 17130<br />

220 kV 18911 19661 21086 22156 23086 26236 30436 36311 39536 42261<br />

132 kV and below 15725 16288 16621 17087 17431 19898 22623 24881 26979 28850<br />

Total 48308 50251 52824 54860 56134 62066 69296 78384 85597 91823<br />

Outlay (Rs crore)<br />

Total outlay 394 333 245 308 228 1054 3680 3762 3188 3011<br />

Evacuation 64 1366 1706 1580 1273<br />

R&M 154 265 233 225 211<br />

A peculiar feature <strong>of</strong> Maharashtra's power system is, location <strong>of</strong> major generating<br />

stations in the eastern part <strong>of</strong> the State at Koradi, Khaperkheda and Chandrapur. Also<br />

major part <strong>of</strong> the State's share <strong>of</strong> power from Central Sector projects is delivered at<br />

Koradi/Chandrapur. Major loads are however located in the western part. Thus, power<br />

is required to be transported over large distance <strong>of</strong> over 700 km, leading to increased<br />

transmission losses. Also, outage <strong>of</strong> any one <strong>of</strong> the five 400 kV circuits between east<br />

and west, or outage <strong>of</strong> a pole <strong>of</strong> HVDC line, results in a bottleneck, hampering proper<br />

operation <strong>of</strong> the transmission system.<br />