23.04.2013 Views

Small Decentralized Hydropower Program National ... - Cd3wd.com

Small Decentralized Hydropower Program National ... - Cd3wd.com

Small Decentralized Hydropower Program National ... - Cd3wd.com

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Generadores El&trims<br />

La selection y ubicacion de1 generador depende de<br />

factores tales <strong>com</strong>a el tipo de turbina y la orientation<br />

de la turbina. Por ejemplo, el generador para una<br />

turbina de tipo bulbo est.5 colocado dentro de1 mismo<br />

bulbo. Por lo general una turbina de tubo requiere un<br />

generador horizontal, y un generador con eje vertical<br />

a engranaje de empuje es adecuado para la mayoria<br />

de las instalaciones de las turbinas Francis. DOS tipos<br />

de generadores, sincronizado y a induction, seran<br />

presentados en 10s parrafos siguientes.<br />

La selection de1 generador, sincronizado o a induc-<br />

cidn, es una funcion de la aplicacion. Un generador a<br />

induction tiene un factor de energia fijo, lo cual setia<br />

una desventaja si se estuviera operand0 una ?equeAa<br />

central de energia, ya que 10s otros generadores en la<br />

central tendtian que suministrar el <strong>com</strong>ponente<br />

reactive para la o?eracih de1 generador de induc-<br />

cion. Los generadores sincronizados pueden variar el<br />

factor de energia y contribuir a la energia reactiva<br />

de las centrales. Se pueden utilizar el ajuste adecuado<br />

de 10s <strong>com</strong>ponentes de 10s genersdores sincronizados<br />

para reducir las pkdidas de las cent&es. La selec-<br />

cih se ta de basar en un analisis dc3 la red de<br />

abastecimiento de energia a la cual el generador con-<br />

tribuira la enc:gia, case por case.<br />

Sincronizado. Un generador sincronizado obtiene<br />

su nombre por estar sincronizado con el voltaje y la<br />

frecuencia de la central antes de cerrar el interruptor<br />

que conecta el generador a la centra! y cuando esti<br />

cone&ado contintia operand0 a velocidad<br />

sincronizada.<br />

Se estimula el generador mediante la aplicacih de<br />

una fuente de corriente directa (dc) a traves de1 em-<br />

bobinado de1 campo de1 rotor y la creation de un<br />

campo magnetico dentro de1 estator que induce un<br />

voltaje potential en la bobina de1 estator. Los disenos<br />

de hoy &a emplean un artefacto de estimulacion<br />

estitica que convierte una fuente de corriente alterna<br />

(ac) a dc por intermedio de un circuito de e&ado<br />

solid0 (solid state). E! sisterma est5tico ha<br />

reemplazado 10s generadores de estinxtlo de corriente<br />

directa movichs por ejes y reiativamente cuesta<br />

menos, tiene un tiempo m6s corto de reaccih y<br />

a<strong>com</strong>oda la descarga de1 campo de energia sin un<br />

resistor de1 campo de descarga cuando se necesite<br />

desconectarlo de stibito. No obstante, para 10s<br />

generadores de 5,000 o menos, a veces todatia se<br />

usan estimuladores a eje sin carbones en vez de1<br />

sistema estitico de estimular. El estimulador sin car-<br />

Electric Generators<br />

The seleclion and location of the generator is<br />

influenced by factors such as turbine type and<br />

turbine orientation. For example, the generator<br />

for a bulb-type turbine is located within the bulb<br />

itself. A horizontal qensrator is usually required<br />

ior a tube turbine ,Ay:d a vertical shaft generator<br />

with a thrust bearin is appropirate for most<br />

Francis turbine installations. Two types of<br />

generators, synchro IOUS and induction, will be<br />

discussed in the following paragraphs.<br />

The choice of generator, synchronous or induc-<br />

tion, is a function of application. An induction<br />

generator has a fixed power factor which, if<br />

operating in a small power system, can be a<br />

disadvantage because other generators in the<br />

system will be required to provide the reactive<br />

<strong>com</strong>ponent for the operation of the induction<br />

generator. Synchronous generators can vary the<br />

power factor and contribute reactive power to the<br />

system. The proper adjustment of reactive <strong>com</strong>-<br />

ponents of synchronous generators can be utiliz-<br />

ed to reduce losses in the system. Selection<br />

should bt: based on a case-by-case analysis of<br />

the power grid to which the generator will con-<br />

tribute power.<br />

Synchronors. A synchronous generator is so<br />

named because it is synchronized to the system<br />

voltage and frequency before the breaker device,<br />

which connects the generator to the system, is<br />

closed and, when connected, continues to<br />

operate at synchronous speed.<br />

The excitation of the generator is achieved by<br />

impressing a direct current (dc) source across the<br />

rotor field eoiis and creating a magnetic field<br />

within the stator which induces a voltago poten-<br />

tial in the stator coils. Present day designs<br />

employ a static excitation device which converts<br />

an alternating current (ac) source to a dc source<br />

via solid state circuitry. The static system has<br />

replaced the shaft-driven de excitation generator<br />

and <strong>com</strong>paratively costs less, has a quicker<br />

response time and ac<strong>com</strong>odates discharge of<br />

the field energy without a field discharge resistor<br />

upon a sudden disconnect of the unit from the<br />

system. However, for generators of 5,000 kW or<br />

less, a brushless shaft driven exciter may still be<br />

used in lieu of a static excitation system. The<br />

brushless exciter is a rotating ac generator with<br />

rectifiers on the main shaft to produce de cur-<br />

rent for the field.<br />

196