Interconeccih con un Sistema de<br />

Distribucih Existente<br />

La interconecci6n de un generador pequefio de<br />

hidroenergia a un sistema de distribucibn existente<br />

debe hacerse con toda consideracibn a la seguridad<br />

contra riesgos, protecci6n el&trica, y la calidad de1<br />

servicio de1 sistema existente.<br />

Un metodo simple para la integracihn de una<br />

unidad pequefia de hidroenergia con un sistema<br />

electric0 existente es el de aislar una porci6n de la<br />

carga de1 sistema existente y servirla s6lamente<br />

desde la estacion hidrkulica. Para efectuar esta<br />

operacidn, la estaciGn debe tener un generador sin-<br />

cronizado. Una llave que normalmente est& abierta se<br />

puede cerrar para servir esta carga aislada de la<br />

fuente existente durante 10s petiodos cuando la<br />

uridad hidraulica esti cerrada. Un sistema “in-<br />

terlock” asegura que la llave no se cierre cuando el<br />

generador est6 en operaci6n. Este arreglo se disefia<br />

en la Figura 3.<br />

Muchas lineas de distribucibn existentes estin pro-<br />

tejidas por re-cerradores que responden a las fallas<br />

mediante breve de-energizacihn de la linea, y luego<br />

volviendo a cerrar para restaurar el servirtio en el<br />

case de que la falla fuere &lo temporaria. Es’s<br />

operacidn puede repetirse hasta trcs veces antes de<br />

que el re-cerrador quede trancado dejando la linea sin<br />

energia. Si una unidad hidrsulica aiimenta direc-<br />

tamente a una linea protejida por un re-cerrador, la<br />

desconecci6n y reconeccibn alternadas pueden<br />

resultar en dtio al generador por causa de1 exceso<br />

de las corrientes o el abrupt0 cambio de torsi6n.<br />

Siempre que se use un re-cerrador cerca de un<br />

generador pequefio, se debe investigar 10s efectos de1<br />

re-cerrador en la operacidn de1 generador.<br />

Cuando se interconecte con un pequeAo sistema<br />

aislado de distribucidn que pudiera tener una<br />

pequefia unidad generadora existente, se debe ex-<br />

aminar las caracteristicas de operaci6n de la unidad<br />

nueva y de la unidad existente para asegurar que<br />

ambas unidades puedan ser operadas paralelamente.<br />

Las caractetisticas de la disminuci6n de la velocidad<br />

deben ser coordinadas para asegurar que un<br />

generador no vaya a “motorizar” al otro.<br />

Cuando se interconecte una unidad hidro&ctrica<br />

pequefia con un sistema existente, y en case de falla<br />

de1 sistema existente, la unidad hidrgulica<br />

suministrara una porci6n de la corriente en falla. En<br />

consecuencia, se debe volver a calcular 10s artefactos<br />

protectores y ajustarlos para tomar en cuenta la cor-<br />

riente adicional en falla. Antes de que 10s traba-<br />

223<br />

When interconnecting with a small isolated<br />

distribution system that may have an existing<br />

small generating unit, the operating<br />

characteristics of the new and existing units<br />

must be examined to ensure that the units can<br />

be operated in parallel. Speed-drop<br />

characteristics must be coordinated to ensure<br />

that one generator will not “motorize” the other.<br />

When a small hydro unit is interconnected with<br />

an existing system, and in the event of a fault on<br />

the existing system, the hydro unit will supply a<br />

portion of the fault current. Hence, the protective<br />

devices must be recalibrated and set to account<br />

for the additional fault current. Before workers<br />

can go out to repair the faulted line, it must be<br />

ensured that the generating unit can not feed<br />

back into the faulted line thus endangering the<br />

public and line crews. Generally, we re<strong>com</strong>mend<br />

that the hydro unit be de-energized and kept out<br />

of service until a faulted line is repaired or safely<br />

isolated from the system.<br />

REA Standards<br />

The United States Rural Elecrrification Ad-<br />

ministration (REA) has printed numerous<br />

specifications, standards, and instructions for<br />

the planning, designing, constructing and<br />

operating rural electric power systems. Over 113<br />

of the electric distribution lines in the U.S. were<br />

built to these specifications. All of these<br />

specifications and standards are available for a<br />

small fee from the Superintendent of Documents,<br />

U.S. Government Printing Office, Washington,<br />

D.C. 20402.<br />

Since 1963, NRECA has worked in over thirty<br />

countries performing services such as initial<br />

surveys, selection of project sites, feasibility<br />

studies, project implementation and follow-up<br />

consulting services to ongoing rural electric<br />

systems. To date, essentially all distributltiir:<br />

systems have been designed according to USA<br />

- REA standards and, where applicable, REA ac-<br />

counting and reporting procedures have been<br />

adopted. By following REA standards, engineer-<br />

ing designs generally provide ample initial<br />

capacity for expansion and development of con-<br />

sumer loads without expensive rebuilding for a<br />

period of ten to fifteen years. Accordingly,<br />

NRECA supervised projects are currently meeting<br />

all load requirements with no foreseeable need to<br />

rebuild backbone facilities.