Small Decentralized Hydropower Program National ... - Cd3wd.com
Small Decentralized Hydropower Program National ... - Cd3wd.com
Small Decentralized Hydropower Program National ... - Cd3wd.com
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
tares de1 circuit0 de la If i ,a son 10s eslabones que<br />
con&an el generador con la red de abastecimiento<br />
de energia. El cierre del interruptor de1 generador<br />
ocurre cuando la unidad esti en sincronismo con la<br />
red de abastecimiento de energa. Estos inierruptores<br />
son tambien activados cdmo mecanismos de interrupcidn<br />
para desconectar la unidad de1 sistema<br />
cuando se presente una condicidn anormal o un paro<br />
normal.<br />
Los interruptores se clasifican por tipo, clase de<br />
voltaje, corriente nominal continua y capacidad de interrupcibn.<br />
Los tipos de interruptores incluyen el<br />
magnetico, sop10 de aire, a gas, aceite y al vacio y<br />
son indicativos de1 medio en el cual se extinque el arco<br />
electrico.<br />
Los interruptores de1 generador para instalaciones<br />
hidroektricas mini y pequenas son <strong>com</strong>unmente a<br />
soplo 1A ,e aire o tipo a! vacio, unidades encerradas en<br />
caja de metal a 4.160 kV. La capacidad de inter-r-up<br />
cion depende de 10s CS&Y.IIOS de “falla” que determinen<br />
la contribution de1 sistema y de1 generador<br />
para constituir una “falla.” Las unidades en cajas de<br />
metal pueden ir equipadas con medidores asociados y<br />
tranformadores de instrumentos.<br />
Hay gabinetes de control y consolxs para todos 10s<br />
interruptores mencionados para 10s circuitos requeridos<br />
para cerrar y soltar el interruptor. Los bujes<br />
vienen con provisiones para transformadores de<br />
instrumentos. Opcionales incluyen equip0 de relevo y<br />
llaves de entrecierre.<br />
Regulador y Equip0 de Control de la Carga. Las<br />
instalaciones hidroelectricas mini y pequenas generalmente<br />
tienen poco efecto sobre la frecuencia de la<br />
red de abastecimiento de energia y se las puede in-<br />
&alar sin regiladores de velocidad, lo cual resulta en<br />
ahorro en el costo.<br />
Para las in&ala&ones hidroelertricas mini o<br />
peqwlas, 10s reguladores que no regulan la velocidad<br />
pueden ser de acciin hidraulica u operadas a electricidad<br />
y su funcion es la de traer la turbina a una<br />
velocidad aproximada a la sincrcnizada para el arranque,<br />
para regular la carga despues de haber obtenido<br />
la velocidad sincronizada y parar el funcionamiento<br />
de la unidad tanto durante condiciones normales<br />
<strong>com</strong>a en case de emergencia. Las unidades deben<br />
estar equipadas con llaves mecanicas para la<br />
velocidad p una fuente de energia independiente que<br />
pueda parar la turbina en case de repulsion de la<br />
carga o p&dida de energfa de la e&c&. Cuando se<br />
utilicen sistemas hidraulicos, se utilizaran<br />
acumuladores de aire-aceite <strong>com</strong>a fuente de energfa<br />
independiente. Cuando se utilicen operadores<br />
electricos, se usaran baterias a corriente directa.<br />
For all aforementioned breakers, control<br />
cabinets and consoles are available for the cir-<br />
cuitry required to close and trip the breaker.<br />
Bushings <strong>com</strong>e with provisions for instrument<br />
transformers. Options include relaying equipment<br />
and key interlocks.<br />
Governor and Load Control Equipment. <strong>Small</strong><br />
and mini-hydroelectric installations generally<br />
have little effect on the frequency of the power<br />
grid and may be installed without speed regula-<br />
tion governors, which results in a cost savings.<br />
For small and mini-hydroelectric installations,<br />
non-speed-regulating governors may be either<br />
hydraulic or electric-operated and their function<br />
is to bring the turbine to near synchronous speed<br />
for start-up, to regulate load after synchronous<br />
speed has been achieved and to shut down the<br />
unit during both normal and emergency condi-<br />
tions. The units must be equipped with<br />
mechanical speed switches and an independent<br />
energy source which will shut down the turbine<br />
in the event of load rejection or loss of station<br />
power. When hydraulic systems are used, an air-<br />
oil accumulator is used as an independent<br />
energy source. When electric operators are used,<br />
a dc battery system is used.<br />
In cases where load regulation is not required,<br />
the turbine is equipped with an inlet valve which<br />
must be able to shut the unit down under<br />
emergency conditions. The power to close the<br />
valve can be provided by a hydraulic accumulator<br />
system, a battery system or a weight trip lever<br />
device.<br />
202<br />
Station Equipment and Protection Systems<br />
Relaying Equipment and Surge Protection. An<br />
important part of hydroelectric plant operations<br />
deals with safety and protection. In particular,<br />
short circuits and ground faults within the plant<br />
must be monitored and corrective action must be<br />
initiated to prevent injury to personnel or damage<br />
to equipment.<br />
Two types of protective devices are the protec-<br />
tion relays and the surge protection arresters.<br />
The relays examine time-current relationships<br />
and operate when the voltage and current<br />
characteristics lie outside of the pre-calibrated<br />
settings. Surge protection is required to restrict<br />
any line surges from the system or any surges in<br />
voltage that have not been properly contained by<br />
the station lightning arresters. The surge ar-<br />
resters are physically located as close to the<br />
generator terminals as possible. The surge equip-