tares de1 circuit0 de la If i ,a son 10s eslabones que<br />

con&an el generador con la red de abastecimiento<br />

de energia. El cierre del interruptor de1 generador<br />

ocurre cuando la unidad esti en sincronismo con la<br />

red de abastecimiento de energa. Estos inierruptores<br />

son tambien activados cdmo mecanismos de interrupcidn<br />

para desconectar la unidad de1 sistema<br />

cuando se presente una condicidn anormal o un paro<br />

normal.<br />

Los interruptores se clasifican por tipo, clase de<br />

voltaje, corriente nominal continua y capacidad de interrupcibn.<br />

Los tipos de interruptores incluyen el<br />

magnetico, sop10 de aire, a gas, aceite y al vacio y<br />

son indicativos de1 medio en el cual se extinque el arco<br />

electrico.<br />

Los interruptores de1 generador para instalaciones<br />

hidroektricas mini y pequenas son <strong>com</strong>unmente a<br />

soplo 1A ,e aire o tipo a! vacio, unidades encerradas en<br />

caja de metal a 4.160 kV. La capacidad de inter-r-up<br />

cion depende de 10s CS&Y.IIOS de “falla” que determinen<br />

la contribution de1 sistema y de1 generador<br />

para constituir una “falla.” Las unidades en cajas de<br />

metal pueden ir equipadas con medidores asociados y<br />

tranformadores de instrumentos.<br />

Hay gabinetes de control y consolxs para todos 10s<br />

interruptores mencionados para 10s circuitos requeridos<br />

para cerrar y soltar el interruptor. Los bujes<br />

vienen con provisiones para transformadores de<br />

instrumentos. Opcionales incluyen equip0 de relevo y<br />

llaves de entrecierre.<br />

Regulador y Equip0 de Control de la Carga. Las<br />

instalaciones hidroelectricas mini y pequenas generalmente<br />

tienen poco efecto sobre la frecuencia de la<br />

red de abastecimiento de energia y se las puede in-<br />

&alar sin regiladores de velocidad, lo cual resulta en<br />

ahorro en el costo.<br />

Para las in&ala&ones hidroelertricas mini o<br />

peqwlas, 10s reguladores que no regulan la velocidad<br />

pueden ser de acciin hidraulica u operadas a electricidad<br />

y su funcion es la de traer la turbina a una<br />

velocidad aproximada a la sincrcnizada para el arranque,<br />

para regular la carga despues de haber obtenido<br />

la velocidad sincronizada y parar el funcionamiento<br />

de la unidad tanto durante condiciones normales<br />

<strong>com</strong>a en case de emergencia. Las unidades deben<br />

estar equipadas con llaves mecanicas para la<br />

velocidad p una fuente de energia independiente que<br />

pueda parar la turbina en case de repulsion de la<br />

carga o p&dida de energfa de la e&c&. Cuando se<br />

utilicen sistemas hidraulicos, se utilizaran<br />

acumuladores de aire-aceite <strong>com</strong>a fuente de energfa<br />

independiente. Cuando se utilicen operadores<br />

electricos, se usaran baterias a corriente directa.<br />

For all aforementioned breakers, control<br />

cabinets and consoles are available for the cir-<br />

cuitry required to close and trip the breaker.<br />

Bushings <strong>com</strong>e with provisions for instrument<br />

transformers. Options include relaying equipment<br />

and key interlocks.<br />

Governor and Load Control Equipment. <strong>Small</strong><br />

and mini-hydroelectric installations generally<br />

have little effect on the frequency of the power<br />

grid and may be installed without speed regula-<br />

tion governors, which results in a cost savings.<br />

For small and mini-hydroelectric installations,<br />

non-speed-regulating governors may be either<br />

hydraulic or electric-operated and their function<br />

is to bring the turbine to near synchronous speed<br />

for start-up, to regulate load after synchronous<br />

speed has been achieved and to shut down the<br />

unit during both normal and emergency condi-<br />

tions. The units must be equipped with<br />

mechanical speed switches and an independent<br />

energy source which will shut down the turbine<br />

in the event of load rejection or loss of station<br />

power. When hydraulic systems are used, an air-<br />

oil accumulator is used as an independent<br />

energy source. When electric operators are used,<br />

a dc battery system is used.<br />

In cases where load regulation is not required,<br />

the turbine is equipped with an inlet valve which<br />

must be able to shut the unit down under<br />

emergency conditions. The power to close the<br />

valve can be provided by a hydraulic accumulator<br />

system, a battery system or a weight trip lever<br />

device.<br />

202<br />

Station Equipment and Protection Systems<br />

Relaying Equipment and Surge Protection. An<br />

important part of hydroelectric plant operations<br />

deals with safety and protection. In particular,<br />

short circuits and ground faults within the plant<br />

must be monitored and corrective action must be<br />

initiated to prevent injury to personnel or damage<br />

to equipment.<br />

Two types of protective devices are the protec-<br />

tion relays and the surge protection arresters.<br />

The relays examine time-current relationships<br />

and operate when the voltage and current<br />

characteristics lie outside of the pre-calibrated<br />

settings. Surge protection is required to restrict<br />

any line surges from the system or any surges in<br />

voltage that have not been properly contained by<br />

the station lightning arresters. The surge ar-<br />

resters are physically located as close to the<br />

generator terminals as possible. The surge equip-