10s voltajes m&s elevados requieren m& material de<br />
aislamiento. Cada transformador va provisto con una<br />
cabina de control y relevo de presi6n stibita. El volta-<br />
je normal para las plantas hidroekctricas mini y pe-<br />
quefias es de 4160 voltios o menos, dependiendo de1<br />
sistema. El cost0 de 10s transformadores se incluyen<br />
con 10s costos de1 patio de distribucibn.<br />
Patio de Distribucidn y otros Equipos<br />
La maniobra y entrega de energia a algunos pun-<br />
tos remotos representan el eslab6n final con la red de<br />
abastecimiento de energia. Aunque a veces no se<br />
toma en cuenta este aspect0 en el planeamiento de<br />
pequefias centrales hidroekctricas, la distancia de<br />
transmisidn de la energia puede ser una restriccidn<br />
ecokmica que puede afectar seriamente la fisibiiidad<br />
de1 proyecto.<br />
Patio de Distribucidn<br />
El patio de distribuci6n <strong>com</strong>prende interruptores<br />
de circuito, llaves de desconeccZn, transformadores,<br />
estructuras, barras colectoras y equipos miscekneos<br />
de la planta de energia. La distribucibn de dichos<br />
equipos debe permitir el movimiento de 10s interrup-<br />
cores de circuit0 y otros equipos mayores en posic%n,<br />
sin ocasionar p&dida de energia en 10s cables y 10s<br />
equipos. Para la instalaci6n de unidades sencillas de<br />
pequefias unidades hidroekctricas, el patio de<br />
distribuci6n ha de ccnsistir en la barra colectora del<br />
generador, el transformador de incremento, la llave<br />
de desconecciGn, un interruptor de1 circuito y una<br />
torre de partida. Se pueden incluir iambi& en el<br />
patio de distribuci6n 10s transformadores de la<br />
estaci6rt, 10s transformadores de1 estimdante y 10s<br />
clibicos para 10s medidores a fin de disminuir el<br />
espacio de piso requerido en la estructura de con-<br />
strucci6n de la planta. Otro arreglo alternativo puede<br />
incltir 10s kkrruptores de1 generador encasillados en<br />
metal (en gabinetes cerrados) ubicados en el patio de<br />
distribuci6n. Un ejemplo tipico de1 disefio de<br />
distribucibn para una planta sencilla se represent-a en<br />
la Fi,gura 10. Se pueden distribuir patios para<br />
unidades multiples de manera similar siempre que se<br />
mantenga la protecci6n ektrica y un medio de<br />
separaci6n entre 10s generadores individuales me-<br />
diante el uso de interruptores de1 generador.<br />
La ubicaci6n de1 patio de distribucidn con relacidn<br />
a la planta depende de la topografia, de las condi-<br />
ciones de1 suelo y de 10s requisitos de espacio. En<br />
cuanto fuere factible geogrkficamcnte, la ubicaci6n<br />
metal-clad (enclosed in cabinets) generator<br />
breakers located in the switchyard. A typical ar-<br />
rangement drawing for a single unit plant is<br />
shown in Figure IO. Multiple unit switchyards<br />
may be similarly arranged as long as electrical<br />
protection and a means for isolation is main-<br />
tained between individual generators by use of<br />
generator breakers.<br />
The location of the switchyard with respect to<br />
the powerhouse is dependent on soil conditions,<br />
space requirements and topography. Where<br />
geographically feasible, the best location of the<br />
switchyard is close to the powerhouse structure.<br />
This eliminates costly extension of the generator<br />
bus and reduces power losses in the bus. Figures<br />
11, 12 and 13 present costs of switchyards vs<br />
plant capacity.<br />
IMiscellaneous Power Plant Equipment<br />
<strong>Small</strong> and mini hydroelectric installations are<br />
generally operated and monitored from a remote<br />
location and therefore designed to house only<br />
the generation equipment. Heating, ventilating<br />
and air conditioning and waste systems fcr<br />
human habitat are normally not required. During<br />
infrequent maintenance periods, bottled water<br />
and portable toilet facilities may be provided.<br />
Ventilation. A central blower located in the roof<br />
or end walls with temperature control to actuate<br />
when ambient temperature rises above 74<br />
deg:ees F is provided. Filtered air inlets near<br />
floor at generator level are also included.<br />
Water System. Duplex pump system with<br />
strainers is provided for water-cooling re-<br />
quirements of the turbine and generator. The<br />
water is taken from the penstock or tailrace. The<br />
cooling water system would operate independant-<br />
ly of the plant generating equipment.<br />
Crane. A permanent powerhouse crane is not<br />
re<strong>com</strong>mended for small hydroelectric plants. Due<br />
to size and cost of equipment, it is considered<br />
more economical to bring in portable equipment<br />
for major plant overhauls.<br />
Miscellaneous. An eye wash bath and a ven-<br />
tilating fan for battery area are required for<br />
safety of the workers.<br />
Fire Protection System. The fire protection<br />
system is a detector-operated CO2 system for ex-<br />
tinguishing fires in generator housings and for<br />
hand-held portable extinguishers for other fire<br />
6ptima seria que el patio de distribuci6n esti cerca de protection.<br />
la estructura qu.e contiene la planta. Esto elimina la Figure 14 contains cost data for estimating the<br />
costosa extensi6n de la barra de colecci6n y reduce cost of miscellaneous power plant equipment.<br />
206