JSN S0920<br />

Name Washer/Disinfector, STM, 1DO, CAB, 26X24X24 Cham<br />

Logistical Category (LOGCAT) Fund Source Weights and Measures (Typical Only)<br />

Army A | Contractor Furnished, Contractor Installed<br />

Navy C | Government Furnished, Government Installed<br />

USAF C | Government Furnished, Government Installed<br />

VA C | Government Furnished, Government Installed<br />

IHS C | Government Furnished, Government Installed<br />

Utilities<br />

NSN 6530<br />

NOTE: Values shown are based on standard typicals used for programming purposes. <strong>The</strong> contractor remains responsible to<br />

develop and coordinate the design / construction in accordance with actual equipment selection.<br />

Utility1: Plumbing F | Cold, hot and treated water and drain<br />

Volts1 208<br />

Utility2: Electrical G | 208/220 volt, 3 phase<br />

Utility3: Med Gas D | Air, high pressure (85 PSIG) max<br />

Utility4: Misc Gas A | Steam<br />

Utility5: Non-Med Gas . |<br />

Utility6: Misc E | Vent to atmosphere<br />

Phase1 3<br />

Phase2 0<br />

Amps1 20<br />

Amps2 0<br />

Weight (lbs) 1200 Weight (kgs) 545<br />

Height (in) 80 Height (cen) 203<br />

Width (in) 44 Width (cen) 112<br />

Depth (in) 36 Depth (cen) 91<br />

Volts2 0<br />

Hertz 50/60<br />

Hertz Dep 0<br />

Hertz Switch -1<br />

BTU / Hour 3500<br />

Watts1 7206<br />

Watts2 0<br />

Description<br />

Unit of Issue EA<br />

Group Sterilizers and Associated <strong>Equipment</strong><br />

A cabinet mounted, single door (vertical sliding w/ tempered glass window), multi-level, mechanical, washer/disinfector, minimum<br />

chamber size 26X24X24, utilizing facility supplied steam. <strong>The</strong> unit is controlled by a microcomputer that monitors and controls all unit<br />

operations and functions and provides both audible and visual indications of deviations. A printer-recorder documents and records each<br />

cycle performance. Processing cycles are pre-programmed with pre-wash, wash/cleaning, rinse, and thermal rinse/disinfection. For use in<br />

health care facilities and laboratories where reusable items (instruments, utensils, anesthesia/respiratory goods, and glassware) are<br />

handled for decontamination purposes. This unit is not a substitute for terminal sterilization. Unit available with manual or power door,<br />

various electrical configurations, options, and accessories. Price based upon power door, 208V, 3-phase, with various options.<br />

Thursday, April 21, 2011 <strong>MIL</strong>-<strong>STD</strong> <strong>1691</strong> | PPMD<br />