JSN L2337<br />

Name Canopy, Hood, Fume, 6 foot<br />

Logistical Category (LOGCAT) Fund Source Weights and Measures (Typical Only)<br />

Army A | Contractor Furnished, Contractor Installed<br />

Navy A | Contractor Furnished, Contractor Installed<br />

USAF A | Contractor Furnished, Contractor Installed<br />

VA A | Contractor Furnished, Contractor Installed<br />

IHS A | Contractor Furnished, Contractor Installed<br />

Utilities<br />

NSN 6640<br />

NOTE: Values shown are based on standard typicals used for programming purposes. <strong>The</strong> contractor remains responsible to<br />

develop and coordinate the design / construction in accordance with actual equipment selection.<br />

Utility1: Plumbing . |<br />

Volts1 120<br />

Utility2: Electrical F | Special electrical requirements<br />

Utility3: Med Gas . |<br />

Utility4: Misc Gas . |<br />

Utility5: Non-Med Gas . |<br />

Utility6: Misc E | Vent to atmosphere<br />

Phase1 1<br />

Phase2 0<br />

Amps1 12<br />

Amps2 0<br />

Weight (lbs) 100 Weight (kgs) 45<br />

Height (in) 21 Height (cen) 53<br />

Width (in) 72 Width (cen) 183<br />

Depth (in) 30 Depth (cen) 76<br />

Volts2 0<br />

Hertz 60<br />

Hertz Dep -1<br />

Hertz Switch 0<br />

BTU / Hour<br />

Watts1 1440<br />

Watts2 0<br />

Description<br />

Unit of Issue EA<br />

Group Laboratory <strong>Equipment</strong><br />

Canopy fumehood. <strong>The</strong> unit includes a switched fan unit with pilot light; corrosion resistant steel, aluminum, or chemical resistant and fire<br />

retardant seamless fiberglass construction; dimensions as indicated on design drawings; fire suppression systems and any other special<br />

requirements to be defined during the facility design. It also includes a 3/4 horsepower motor blower. <strong>The</strong> static pressure loss shall not<br />

exceed 0.91 at 1290 cfm and 1.65 at 1935 cfm. It is equipped with baffles to maximize slot velocities and control fumes. Used in<br />

laboratories for low to moderate risk biological agents. Other sizes may be available. Blower motor mounted separate from the canopy<br />

and may not be included in the size specification.<br />