JSN A1120<br />

Name Column, Service, Prefab, Surgical, Ceiling Mounted<br />

Logistical Category (LOGCAT) Fund Source Weights and Measures (Typical Only)<br />

Army A | Contractor Furnished, Contractor Installed<br />

Navy A | Contractor Furnished, Contractor Installed<br />

USAF A | Contractor Furnished, Contractor Installed<br />

VA A | Contractor Furnished, Contractor Installed<br />

IHS A | Contractor Furnished, Contractor Installed<br />

Utilities<br />

NSN 6530<br />

NOTE: Values shown are based on standard typicals used for programming purposes. <strong>The</strong> contractor remains responsible to<br />

develop and coordinate the design / construction in accordance with actual equipment selection.<br />

Utility1: Plumbing . |<br />

Volts1 120<br />

Utility2: Electrical F | Special electrical requirements<br />

Utility3: Med Gas G | Oxygen, vacuum and medical air (50 PSIG)<br />

Utility4: Misc Gas D | Nitrogen and nitrous oxide gas<br />

Utility5: Non-Med Gas . |<br />

Utility6: Misc . |<br />

Phase1 1<br />

Phase2 0<br />

Amps1 20<br />

Amps2 0<br />

Weight (lbs) 0 Weight (kgs) 0<br />

Height (in) 0 Height (cen) 0<br />

Width (in) 0 Width (cen) 0<br />

Depth (in) 0 Depth (cen) 0<br />

Volts2 0<br />

Hertz 60<br />

Hertz Dep -1<br />

Hertz Switch 0<br />

BTU / Hour 0<br />

Watts1 2400<br />

Watts2 0<br />

Description<br />

Unit of Issue EA<br />

Group Architectural<br />

Prefabricated surgical service column. Strong 18 gauge stainless steel shell ceiling mounted unit with the following services: oxygen,<br />

nitrous oxide, nitrogen, medical air, medical vacuum, gas evacuation, electrical outlets, monitoring connectors, and IV holders. Specify<br />

type of column (fixed or retractable) and number of outlets required for each service. Size will vary with number of service outlets<br />

required. <strong>Design</strong>ed to be used in the operating room, recovery and ICU-CCU rooms.<br />

Thursday, April 21, 2011 <strong>MIL</strong>-<strong>STD</strong> <strong>1691</strong> | PPMD<br />