JSN L2200<br />

Name Hood, Fume, Floor Standing<br />

Logistical Category (LOGCAT) Fund Source Weights and Measures (Typical Only)<br />

Army A | Contractor Furnished, Contractor Installed<br />

Navy A | Contractor Furnished, Contractor Installed<br />

USAF A | Contractor Furnished, Contractor Installed<br />

VA A | Contractor Furnished, Contractor Installed<br />

IHS A | Contractor Furnished, Contractor Installed<br />

Utilities<br />

NSN 6640<br />

NOTE: Values shown are based on standard typicals used for programming purposes. <strong>The</strong> contractor remains responsible to<br />

develop and coordinate the design / construction in accordance with actual equipment selection.<br />

Utility1: Plumbing I | Drain only<br />

Volts1 120<br />

Utility2: Electrical B | 120 volt, special outlet<br />

Utility3: Med Gas . |<br />

Utility4: Misc Gas . |<br />

Utility5: Non-Med Gas . |<br />

Utility6: Misc E | Vent to atmosphere<br />

Phase1 1<br />

Phase2 0<br />

Amps1 15<br />

Amps2 0<br />

Weight (lbs) 756 Weight (kgs) 344<br />

Height (in) 98 Height (cen) 249<br />

Width (in) 49 Width (cen) 124<br />

Depth (in) 35 Depth (cen) 89<br />

Volts2 0<br />

Hertz 60<br />

Hertz Dep -1<br />

Hertz Switch 0<br />

BTU / Hour 0<br />

Watts1 1800<br />

Watts2 0<br />

Description<br />

Unit of Issue EA<br />

Group Laboratory <strong>Equipment</strong><br />

Floor standing fume hood. <strong>The</strong> unit presented is 4 Ft but is available in other sizes. It will include a fluorescent light fixture, blower switch<br />

with pilot light, at least one duplex receptacle, a cup sink and shall be acid resistant. <strong>The</strong> minimum average face velocity shall be 100 fpm.<br />

It Includes a safety glass sash resistant to heat of up to 71 degrees centigrade. Static pressure loss is not to exceed 0.22 inches. <strong>The</strong> fume<br />

hood also has adjustable baffles. Other custom options are available. Used in laboratories to prepare samples requiring the use of toxic<br />

and or flammable materials.<br />